Loading...
Ord. 0116 1965-03-16BUILDING CODE OF THE CITY OF PEARLAND PEARLAND, TEXAS AN ORDINANCE TO BE CALLED "BUILDING CODE OF THE CITY OF PEARLAND" CREATING A BUILDING CODE PRESCRIBING DUTIES AND QUALIFICATIONS OF INSPECTORS; TO BE SUPERVISED BY GENERAL BUILDING BOARD OF FIVE MEMBERS; PROVIDING FOR PERMITS DOING OR CAUSING TO .uE DONE CONTRACT WORK; PRESCRIBING FEES; PROVIDING EXCEPTIONS; REGULATING QUALITY; TYPE AND KIND OF MATERIAL AND MANNER OF INSTALLATION REFERRING TO SOUTHERN STANDARD BUILDING CODE AND ADOPTING SAME; PROVIDING FOR APPOINTMENT OF BUILDING INSPECTOR AND INSPECT ION OF ALL BUILDING. THIS BUILDING CODE INCLUDES METES AND BOUNDS OF THE CITY OF PEARLAND. ALL BUILDINGS AND REMODELING MUST HAVE BUILDING PERMIT AND MUST ACQUIRE IT FROM CITY SECRETARY OR TAX DEPARTMENT. ON REMODELING OF HOMES, OWNER MUST HAVE ET.RCTRICAL AND PLUMBING INSPECTORS. THERE WILL BE NO CHARGE IF CONTRACT DOES NOT EXCEED $1,000.00. PERMIT FEES SHALL BE S1.00 PER $1,000.00.BASED ON CONTRACT PRICES. THE BUILDING INSPECTOR MUST MAKE AN INSPECTION BEFORE THE SLAB IS POURED; AFTER BUILDING DRIES IN S0 INSPECTOR CAN SEE CORNER BRACES, COLLAR BRACES AND RAFTERS, AND TYPE OF MATERIALS USED. FINAL INSPECTION AFTER JOB IS COMPLETED. THIS ORDINANCE IS NOT INTENDED TO SUPERSEDE OTHER EXISTING GOVERNMENTAL REGULATIONS SUCH AS STATE, COUNTY OR FEDERAL REQUIREMENTS. CONTRACTS SIGNED PRIOR TO MARCH 24, 1966 NOT AFFECTED BY THIS ORDINANCE. Page - 1 - gBOTIOt.. 1. BUILDING INSPECTOR 1. Appointment. (a) The office of building inspector is hereby created and the executive official in charge shall be known as the building inspector. (b) It shall be unlawful for any building inspector to engage in, or have any financial interest in any concern engaged in, the business of sale, installation, construction or main- tenance of buildings, or the sale of real estate in the City of Pearland either directly or indirectly, at any time while holding the position of building inspector for the City of Pearland. (c) During temporary absence or disability of the building inspector the appointing authority shall designate an acting building inspector. 2. Duties - It shall be the duty of the building inspector to enforce all laws relating to the construction, altera- tion, removal, and demolition of buildings and structures. 3. Rules. (a) The building inspector shall promulgate rules as prescribed in this code and consistent therewith, it being the intent of this requirement that the standards! of federal or state bureaus, national te'chnicai organization or fire underwriters, as the same may be amended from time to time, shall serve as a guide in fixing the minimum rules of practice under this code. (b) For the purpose of securing for the public the benefits of new developments in the building industry and yet in- suring public safety, the building inspector shall make or cause to be made investigations, or may accept duly authenticated reports from recognized sources, of new materals or modes of construction, intended for use in the construction of buildings or structures in the municipality which are not provided for in this code, and shall promulgate rules settingfOrththe conditions under which such materials or modes of construction may be used: (c) No rule of the building inspector shall become effective until four weeks after notice of intention to enforce it shall have been given through the publication in a newspaper in general circulation in the municipality and until a public hearing on the same shall have been held; provided that said public hearing shall not be necessary unless a request shall have been made for such hearing during the said period of publication Such rule shall be drawn in its proposed form and open to public inspection at the time the notice to enforce is published. (d) Rules promulgated as herein provided shall have the same force and effect as provisions of this code. (e) Any rule may be amended or repealed by the same procedure prescribed for the adoption of new rules. SECTI.OI{ 2. PERMITS, INSPECTION, AND POSTING OF LIVE LOADS (a) No building or structure shall hereafter be built, enlarged, altered or moved without a permit from the building inspector,who may require a plan of the proposed work, together with a statement of the materials to be used. (b) The building inspectorshall inspect all buildings or structure during construction to see that the provisions of law are complied with and that construction is prosecuted safely. Whenever in his opinion, by reason of defective or illegal work in violation of a provisions of this code the continuance of a building operation is contrary to public welfare, he may order all further work to be stopped and may require suspension of work until the condition in violation has been remedied, (c) The live load for which each floor, or part of a floor, of a business building or storage building is designed and approved shall Le conspicuously posted in that part of the story to which it apflies. SECTION 3. SUPPLII'NTARY REQUIREMENTS The 196C-1961 Edition of Southern Standard Building Code shall be deemed to be the generally accepted good practice for all matters not covered by this code. SECTION 4. UNSAFE BUILDINGS Page - 2 - (a) A building or structure that may be or shall be found upon inspection to have become dangerous or unsafe, shall, unless made safe and so certified by the building inspector, be taken down and removed. (b) A building or structure declare unsafe by duly constituted authority set up by the municipality may be restored to safe condition; provided that if the damage or cost of recon- struction or restoration is in excess of 50% of the value of the building or structure, exclusive of foundations, such building or structure, if reconstructed or restored, shall be made to conform with respect to materials and type of construction, to the requirements for buildings and structures hereafter erected; but no change of use or occupancy shall be compelled by reason of such reconstruction or restoration. The term unsafe building shall include buildings structurally unsafe, unstable or un- sanitary; inadequately provided with exit facilities; constituting a fire hazard; unsuitable or improper for the use and occupancy to which they are put; constituting a hazard to health or safety because of inadequate maintenance, dilapidation, obsolescence or abandonment; or otherwise dangerous to life or property. SECT,$ON,:54 PENALTY FOR VIOLATIONS. (a) A person who shall violate a provision of this code or fail to caitiply therewith or with any of, the requirements thereof, or who shall erect; construct, alter oi' repair, or has erected, constructed, altered or repaired a building or structure, in violation of a detailed statement or plan submitted and approved thereunder; or of a permit of certificate, issued thereunder, shall be guilty of a misdemeanor punishable by a fine of not less than five dollars nor more than two hundred dollars and each day that the said violation shall continue shall be deemed a separate offense. (b) The owner of a building, structure or premises, where anything in violation of this code shall be placed or shall exist, and an architect,bizilder, contrator, agent, person or cor- poration employed in connection therewith and who may have assisted in the commission of such violation shall beo,ilty of a separate offense and upon conviction thereof shal]iebeined as therein provided. (c) The imposition of the penalties herein prescribed shall not preclude the corporation counsel from instituting an appropriate action or proceeding to prevent an unlawful erection, construction, reconstruction, alteration, repair, conversion, maintenance or use, or to restrain, correct or abate a violation, or to prevent the occupancy of a building, structure or premises, or to prevent an illegal act, conduct, business or use in or about any premises. SECTION 6. DEFINITIONS Alteration, as applied to a building or structure, means a change or rearrangement in the structural parts or in the exit facilities; or an enlargement, whether by extending on a side or by increasing in height or the moving from one location or position to another; the term "alter"in its ;various moods and tenses and its participial forms, refers to the making of an alteration. Amusement device means a mechanically operated device which is used to convey persons in any directions as a form of amusement. Apartment means a room, or a suite of two or more rooms, in a residence building occupied as the home or residence of an individual,family or household. Approved, as applied to a material, device or mode of construction, means approved by the building insgec.tor under the provisions of this con;, or by other authority designated by law to give approval in the matter in question. Area, as applied to the dimensions of a building, means the maximum horizontal projected area of the building at grade. Automatic fire alarm system means a system which automatically detects a fire condition and actuates a fire alarm signal device. Page - 3 - Basement means a story with floor level 2 feet or more below finished grade. Brick means a solid masonry unit having a shape app- roximating a rectangular prism, not larger than 12 by 4 by L. inches. A brick may be made of burned clay or shale, of lime and sand, of cement and suitable aggregates, or of fire clay or other approved materials. Building means a combination of materials to forma construction that la safe and stable, arld adapted to permanent or continuous occupancy for public, institutional, residence, business or storage purposes; the term"building" shall be con- strued as if followed by the words "or part thereof." For the purposes of this code, each portion of a building separated from other portions by a fire wall shall be considered as a separate building. Building Inspector means the Officer or other desig- nated authority charged with the administration and edfdreement of this code, or his duly authorized representative, Dwelling means a building occupied exclusively for residence purposes and having not more than two apartments, or as a boarding or rooming house serving not more than 15 persons with meals or sleeping accommodations or both. Fire resistance rating means the time in hours that the material or construction will withstandthe standard fire exposure as determined by a fire test made in conformity with the "Standard Methods of Fire Tests of Building Construction and Materials;': ASTM E119-47. Fire retardant ceiling means a ceiling construction which has been proved by test as satisfactory for use as ceiling protection for a floor or roof construction which has a fire resistance rating of not less than one hour. Fire retardant treated lumber means lumber which has been treated by pressure impregnation process to give a flame spread classification of 50 or less according to the method for the "Fire Hazard Classification of Building Material" of Underwriters' Laboratories, Inc., and which is shown to be so classified by a certificate or label issued by Underwriters' Laboratories. Garage means a building, shed or enclosure, or a part thereof, in which a motor vehicle containing a flammable fluid in its fuel storage tank, is stored, housed, kept or repaired. Grade,with reference to a building, means, when the curb level has been established, the mean elevation of the curb level opposite those walls that are located on, or parallel with and within 15 feet of, streetlines; or, when the curb level has not been established, or all the walls of the building are more than 15 feet from street lines, "grade" means the mean elevation of the ground adjoining the building on all sides. Habitable room means a room occupied by one or more persons for living, eating or sleeping; and includes kitchens serving apartments or individual households, but does not include bathrooms, toilet compartment,laundries, serving and storage pantries, corridors, basement and other spaces that are not used frequently or during extended periods. Height, as applied to a building, means the verticle distance from grade to the highest finished roof surface in the case of flat roofs, or to a point at the average height of roofs having a pitch of more than one foot in LI-2 feet; "height" of a building in stories does not include basements, except that in school buildings of ordinary, noncombustible or wood frame construction, the basement shall be deemed a story when used for purposes other than storage or heating. Height, as applied to a wall, means the vertical distance to the top measured from the foundation wall, or from a girder or ether immediate support of such wall. Hollow masonry unit means a masonry unit whose net eras^ sectional area in cnlz plane parallel to the bearing surface is less than 75 per cent of its gross cross -sectional area meas- ured in the same plane, Lot means a portion or parcel of land considered as a unit, devoted to a certain use or occupied by a building or a group of buildings that are united by a common interest or Page-4- Lot line means a line dividing one lot from another, or from a street or other public space. Masonry means brick, stone, plain concrete, hollow block, solid block or other similar building units or materials, or combinations of them, bonded together with mortar. Reinforced concrete is not classed as masonry. Multifamily house means a building occupied as the home or residence of individuals, families or households living independently of each other, of which three or more are doing cooking within their apartments; including tenement house, apartment house, flat. Municipality means the governmental unit which has ad- opted this code under the legislative authority. Place of assembly means a room or space in which provision is made for the seating of one hundred or more persons for religious, recreational; educational, political, social or amusement purposes or for the consumption of food or drink. Such room or space shall include any occupied connection room or space in kthe same story or in a story or stories above or below, where entrance is common to the rooms or spaces. Prefabricated means composed of sections fabricated prior to erection on building foundation. Shaft means a vertical opening or passage through two or more floors of a building or through floors and roof. Solid mason= means masonry consisting of solid masonry units laid continuously with the joints between the units filled with mortar, or consisting of plain concrete. Solid masonry unit means a masonry unit whose net cross -sectional area in every plane parallel to the bearing surface is 75 per cent or more of its gross cross -sectional area measured in the same plane. Sprinklered means equipped with an approved auto- matic sprinkler system properly maintained. Street means any public thoroughfare, street, avenue, boulevard, park, lane, terrace, concourse or space 20 feet or more in width which has been dedicated or deeded to the public for public use. Walls: bearing wall means a wall which supports any vertical load in addition to its own weight; cavity wall means a wall built of masonry units or of plain concrete, or a combination of these materials, so arr- anged as to provide an air space within the wall, and in which the inner and outer parts of the wall are tied together with metal ties; faced wall means a wall in which the masonry facing and backing are so bonded as to exert common action under load; fire a.rtition means a partition constructed with section for the purpose of restricting the spread of fire or to provide an area of refuge, but not necessarily continous through all stories nor extended through the roof. fire wail means a wall constructed in accordance with section for the purpose of subdividing a building or separating buildings to restrict the spread of fire and which starts at the foundation and extends continuously through all stories to and above the roof, except where the roof is fireproof or semifireproof and the wall is carried up tightly against the under side of the roof slab. foundation wall means a wall below the first floor ex- tending below the adJ;oent ground level and serving as support for wall, pier, column or other structural part of a building; hollow wall of masonry means a wall built of masonry units so arranged as to provide an air space within the wall, and Page-5- in which the inner and outer parts of the wall are bonded to- gether with masonry units* non -bearing wall means a wall which supports no load other than its own weight; panel wall mean a non -bearing wall built between columns or piers aid wholly supported at each story; party wall means a wall used or adapted for joint ser- vice between two buildings. veneered wall means a wall having a facing which is not attached and bonded to the backing so as to form an integral part of the wall for purposes of load bearing and stability. SECTION 7. CLASSIFICATION OF OCCUPANCIES 1. Classes designated. For the purposes of this code, buildings are classified, with respect to occupancy and use, es public buildings and storage buildings. (a) Public building means a building in which persons congregate for civic, political, educational, religious, social or recreational purposes, including among others,armories, assembly halls, auditoriums, bath houses, bowling alleys, churches, city halls, club rooms, colleges, court houses, dance halls, ex- hibition buildings, grandstands, gymnasiums, lecture halls, libraries, lodge rooms, motion picture theaters, museums, passen- ger stations, recreation piers, restaurants, schools, skating rinks, stadium and theaters. (b) Institutional building means a building in which persons are harbored to receive medical, charitable or other care or treatment, or in which persons are held or detained by reason of public or civic duty, or for correctional purposes, including among others, asylums, homes for the aged, hospitals, houses of correction, infirmaries, jails, nurseries, orphanages, penal institutions, reformatories and sanitariums. (c) Residence building4 except when classed as an institutional building, means a building in which sleeping accomodations are provided; incuding among others, apartments, club houses, convents, dormitories, dwellings, hotels, lodging houses, multifamily houses, studios and tenements. (d) Business building means a building occupied for the transaction of business, for the rendering of professional services, for the display or sale of goods, wares or merchandise, or for the performance of work or labor; including among others, banks, bakeries, barber shops, chemical laboratories, creameries, electric substations, factories, gasoline service stations, ice plants, laboratories, laundries, markets, office buildings, open air stores, power plants, radio stations, smoke houses, stores, telephone exchanges, television station and work shops. (e) Storage building means a building for the housing, except for purely display purposes, of airplanes, automobiles, railway cars or other vehicles of transportation, for the sheltering of horses, livestock or other animals, or exclusively for the storage of goods, wares, or merchandise, not excluding in any case offices incidental to such uses; 1 including among others, barns, cold storage, freight depots, garages, gasoline bulk stations, grain elevators, hangars and storage warehouses. 2. Mixed Occupancy. Where a minor portion of a building is used for office, study, studio or other similar purpose, the building shall be classified as to occupancy on the basis of the major use. In other cases where a building is occupied for two or more purposes not included in one class, the provisions of this code applying to each class of occupancy shall apply to such parts of building, as come within that class; and if there should be conflicting provisions, the requirements securing the greater safety shall apply. 3. Douhtful Clnssification. In case "' a building is not specifically p:c ovided for or where there is an uncertainty as to its classificat on, its status shall be fixed by a duly promulgated rule giving due regard to safety. SECTION 8. CLASSIFICATION OF CONSTRUCTION 1. Types design ted. For the purposes of this code, construction as used in buildings shall be classified as follows: (a) Fireproof construction (b) Semifireproof construction (c) Heavy Timber construction (d) Ordinary construction (e) Noncombustible construction (f) Wood frame construction (g) Unprotected metal construction SECTION 9. SPECIAL OCCUPANCY REQUIREMENTS: 1. Institutional buildings (a) Institutional buildings for occupants involuntarily detained or bedridden shall be of fireproof construction or semifireproof construction. (b) Institutional buildings for occupants which are not involuntarily detained or bedridden, when of other than fire- proof construction or semifireproof construction, shall not exceed 2 stories in height and shall have floors and partitions with fire resistance ratings of not less than one hour and with fire retardant ceilings under roofs, and if of wood frame construction shall not exceed 1 story in height nor 2500 square feet in area; provided that buildings converted from another occupancy to such occupancy shall be exempt from these restrictions if sprinkler- ed. 2. Theatres and motion picture theatres. (a) Theatres and motion picture threatres shall be fireproof construction or semifireproof construction, except that portions of such buildings not over 1 story or over 45 feet in height may have combustible roof construction if protected by fire retardant ceilings. (b) No theatre or motion picture theatre shall be located within or attached to a building or other occupancy unless it is separated from such other occupancies by walls and floors of non-combustible construction having fire resistance rating of not less than 3 hours. 3. Schools, colleges, assembly halls, dance halls, bowling alleys, and auditoriums over one story in height shallhave floors of not less than one -hour fire resis- tance. 4. wall and ceiling finish. In public buildings and institutional buildings, and in all places of assembly and exit ways therefrom, no combustible material shall be used as interior wall or ceiling finish which if of such a nature that flame will spread over its surface more rapidly than over one -inch (nominal) wood boards covered with ordinary paint or varnish. 5. Business and residence separation. In buildings of other than fireproof or semifireproof construction portions classified as of business occupancy shall be separated from portions classified as of residence occupancy by partititions having a fire resistance rating of not less than one hour and by fire retardant ceilings, unless the business portion is sprinklered. 6. Separation of dwellings. Walls or partitions separa- ting 2 or more dwellings of other than fireproof or semifireproof construction shall consist of a form of construction having a fire resistance rating of not less than 1 hour. 7. Partititions in multifamily houses. In multifamily houses partitions separating apartments or apartments from hallways or apartments from other occupancies and partitions separating stores from hallways or other occupancies shall have a fire resistance rat:i_r..g of not less than 1 hour, with openings equipped with approves' lire doors or with substantial metal or metal covered doors or solid wooden doors of the flush type of nominal thickness not less than 1-3/4 inch. SECTION 10. FIGHT RESTRICTIONS. 1. New Buildings. Except as may be otherwise provided in subsection tl of this section, no building hereafter erected shall exceed in height the limits fixed in this section. 2. Alterations. No building shall hereafter be altered so as to exceed the limits of height fixed by this section. 3. Public Buildings. For public buildings semifire- proof construction shall not exceed 75 feet, except that public buildings which have an occupancy of less than 100 persons above the 75 foot level may be unlimited in height; heavy timber con- struction, 4 stores .or 55 feet; and ordinary construction and non-combustible construction 3 stories . or 35 feet, except that churches or such construction may be 45 feet but not more than 2 stories, and that schools of such construction shall be not more than 2 stories high;. 4. Institutional buildings. For institutional buildings semifireproof construction shall not exceed 75 feet; ordinary construction, heavy timber construction and noncombustible con- struction shall not exceed 2 stories or 35 feet. 5. Residence buildings. For residence buildings, heavy timber construction shall not exceed 75 feet; ordinary construction and non-combustible construction shall not exceed 3 stories •or 45 feet; provided that when the floor immediately over basements are of noncombustible construction having a fire 'resistaieernating of not,less.than2 hours, ordinary construction may exceed these heights but shall not exceed 4 stories or 55ieet and when in addition, in multifamily houses which are subdivided by fire partitions into floor areas not exceeding 34500 square feet, all other floors have a fire resistance rating of not less than one hour, ordinary construction may be, but shall not exceed 5 stories .or 65 feet. Wood frame construction and unprotected metal construction shall not exceed 2 stories ror 35 feet; except that dwellings other than prefabricated dwellings shall not exceed 3 stories. 6. Business building_ For business buildings semi - fireproof construction and heavy timber construction shall not exceed 75 feet except that the office building semifireproof construction shall be unlimited; and ordinary construction and noncombustible constru ction shall not exceed 4 stories ;or 50 feet. 7. Storage buildings. For storage buildings semi - fireproof construction shall not exceed 50 feet; ordinary construction, heavy timber construction and hon-2oralusitible constr shall not exceed 35 feet ; provided that in buildings that uction are sprin.klered;:'semifireprodf and he'avytti"mber construction shall not'.cxceed 75 feet and ordi'nary construction And 'noncombustible conatruction shall not exceed 50 feet; and wood frame construction and unprotected metal construction shall not exceed one story or 35 ft.E.NCEPTION:aForthe purpose of this section, the following appurtenances shall not be deemed part of buildings; church spires, tanks and their supports, roof structures, chimneys, signs attached to the building, radio masts, water cooling towers for air conditioning or other apparatus, and parapets that do not extend more than 4 feet above the roof surface at their point of contact. (b) Outside the fire zone limits, public buildings, business buildings, or storage buildings may, in the discretion of the governing body of the municipality, be erected to greater heights than fixed by this section. SECTION 11. LIGHTS AND VENTILATION 1. (a) natural light directly on a this section. (b) Such rooms shall be not less than 7 feet wide in any part, and shall contain not less than 70 square feet of gross floor area. Such rooms shall have a clear height of not less than 7 feet 6 inches for at least 60 square feet of floor area. 2. Other rooms. Every room, other than a habitable room, used or occupied by persons, except storage rooms with Habitable rooms. Every habitable room shall be provided with and ventilation by one or more windows, opening street or on a court conforming to subsection of • Page - 8 - infrequent occupancy, shall be provided with one or more windows or ventilating skylights opening directly on a street or on a court conforming to subsection of this section; or such rooms shall be provided with an approved means of mechanical ventilation. 3. Access to rooms and waterclosets. (a) In multifamily houses hereafter erected or altered access shall be had to living rooms, kitchens and bedrooms with- out passing through a bedroom. (b) Access without passing through a bedroom shall also be provided to at least one water closet, unless every bed- room has direct connection with a water closet or bathroom having water closet accomodation. SECTION 12. MEANS OF EGRESS 1. Application of section. Buildings hereafter erected, except dwellings, shall be provided with exit facilities in accordance with the requirements of this section. No building shall be altered so as to reduce the number or capacity of exits to less than required for new buildings. 2. Exit way defined. (a) "Exit way" means the exit doorway or doorways, or such doorways together with connecting hallways or stairways, either interior or exterior, or fire escapes, by means of which persons may proceed safely from room or space to a street or to an open space which provides safe access to a street. Exit ways from any room may lead through other roomsof the same tenancy. (b) Two or more separate exit ways may use the same corridor or hallway,provided that such corridor or hallway is enclosed by and separated from exit stairways and other parts of the building by partitions having a fire resistance rating of not less than one hour. 3, Number of occupants. (a) The dimensions and capacity of exit ways shall be proportioned to the number of persons to be accomodated. (b) When the number of persons to be accomodated by the exit way is not stated in the application for a permit or is not otherwise fixed, it shall be decided on the basis of the gross area of the space devoted to a particular purpose and shall be assumed to be as follows: Occupancy Gross Area Per Person Dance hall, lodge room, or place of assembly 15 sq. ft. Store -street floor and sales basement 30 sq. ft. other floors 60 sq. ft. Space used for occupancies not listed above: Public 40 sq. ft. Institutional 150 sq_. ft. Residence 125 sq. ft. Business 100 sq. ft. Storage 300 sq. ft. 4. Number of Exits. (a) From rooms. Every room having an area exceeding 1,000 square feet or occupied by more than 100 persons shall haze at least two exit ways. (b) From Stories. Every story shall have at least one exit way and every story that exceeds 2,500 square feet in area shall have at least two separate exit ways. (c) Apartments. In multifamily houses exceeding two stories above the basement, and in every two-story multifamily house having more than 6 apartments using a common exit way, every apartment that has not direct exit to a street or to a court opening on a street, shall have access to at least one additional exit way separated fr.^mn and independent of the primary interior stairway or fire tower. 5. Locet^.nn of exit doorways. Exit doorways shall be so located that no point in a floor area, room or space served by them is more than 100 feet distant from an exit door- way, measured along the line of travel; except that when a floor area is subdivided into smaller area, such as rooms in hotels, multifamily houses, and office buildings, the distance from the Page - 9 - door of any room, along an unobstructed hallway, to an exit door- way, shall be not more than 125 feet, except that hallways above the first story shall not extend beyond an exit as a dead end more than 50 feet. where the building is of fireproof construc- tion or semifireproof construction, or the building is sprinklered, the above distances may be increased 50 per cent. 6. Enclosures of interior stairways. (a) All interior stairways in buildings connecting two or more stories, whether required as exits or not, shall be enclosed, except as otherwise provided in paragraph (d). (b) In unsprinklered buildings which exceed 30 feet to the floor of the topmost story, or are occupied by more than 75 persons above, or 40 persons below, the first story above grade, not counting those in the first story, and in multifamily houses 4 stores or more in height, interior required stairways shall be enclosed with fire partitions. (c) In other buildings interior stairways shall be enclosed in partitions having a fire resistance rating of not less than one hour. In buildings of fireproof construction and semifireproof construction such partititions shall be noncombustible (d) An enclosure shall not be required for: (1) A flight of stairs from the main entrance floor to the floor next above when such stairs are not a part of required stairway. (2) A flight of stairs in a building of fire- proof construction, semifireproof construction, or a sprinklered building of heavy timber construction or ordinary construction or noncombustible construction, when such stairs connect only the story with one other story immediately above or below it. In such case the upper end of the stairway shall not connect to a hallway serving as an exit except through afire door. (3) A flight of stairs from a balcony or mezzanine having an area not exceeding 25 per cent of that of the floor immediately below. (e) Openings. No openings except the necessary doorways, and windows opening to the exterior of the building, shall be permitted in a stair enclosure required by this section. Such doorways shall be equipped with approved self -closing fire doors, except that when fire partitions are not required for the enclosure, substantial self -closing metal or metal covered cdoorsor solid wooden doors of the flush type of nominal thick- ness not less than 1-3/4 inches may be used. In school buildings, doors on openings in stair enclosures may have wired glass panels; the area of such glass in any one door shall not exceed 720 square inches. 7. Width of interior stairways. The minimum unobstructed width of a stairway serving as a required exit shall be not less than 44 inches; provided that in multifamily houses and storage buildings, and in other buildings occupied by a single tenant and limited in occupancy to 40 persons, such width may be 36 inches. The width of stairs shall be measured between hand rails except where hand rails project not more than 3 z inches into such width. 8. Treads and risers. (a) Treads and risers of required stairs shall be propertioned that the product of the width of tread, exclusive of nosing, and the height of riser, in inches, shall be not less than 70 nor more than 75; but risers shall not exceed 7-3/4 inches in height, and treads, exclusive of nosing, shall be not less than 9 z inches wide; except that in schools the proportion and dimensions of the treads and risers may, in the discretion of the building inspector, be adjusted to suit the age of the pupils for which the school is intended. Treads and risers shall be of uniform width and height in any one story. (b) The use of winders is prohibited in required stairways. 9. Landings. (a) niffit of stairs shall have a vertical rise of more than 12 feet between floors or landings except that in stairways serving as exits in public buildings such verticle rise shall not exceed 8 feet. (b) The length and width of landings shall be not less than the width of stairways in which they occur. Page -10 - 10. Handrails. (a) rxcept for steps in aisles, stairs shall have walls or well secured barricades or guards on both sides. (b) Such stairs when less than 44 inches in width shall have handrails oh at least one side. (c) Such stairs when required to be !WI inches or more in width shall have handrails on both sides. (d) When the required width of a flight of stairs exceed 96 inches, an intermediate handrail, continuous between landings, securely supported and terminating at the upper end in newels or standards with no projections shall be provided. 11, Exit hallways. The clear width of every hallway or passage leading to a required exit shall be hot less than at the rate of 12 inches for every 100 persons to be accommodated by,the hallway but not less than 44 inches; provided that in multifamily houses or in case less than 40 persons are to be accommodated, the minimum clear width may be 36 inches, 12. Width of doorways. The aggregate clear width of doorways serving as required exits shall be not less than at the rate of 22 inches for every persons to be accommodated. No exit doorway serving as an exit for more than 40 persons shall have a clear width of less than 34 inches (normal 36-inch door.) 13. Hanging of doors. (a) The doors of required doorways shall be so hung• and arranged that when fully opened they will not in any way diminish or obstruct the required width of hallway, stair, or other means of exit. (b) Doorways opening onto a street or to a court or open space communicating with a street, and serving as a required exit way for more than 40 persons shall have the doors, including the doors of vestibules, so hung as to swing open in the direction of exit travel; but this requirement shall not be construed to prohibit the use of sliding doors in stables, garage or shipping and receiving rooms of business building and storage buildings. (c) All exit doors in rooms occupied by 40 or more persons and all exit doors in exit ways from places of assembly shall be hung to swing open in the direction of exit travel. (d) No exit door shall open immediately on a flight of stairs but a landing the length and width of which are not less than the width of such door, shall be provided between such door and such stairs. (e) Where the size of the exit doorway requires two doors in the same opening, the doors shall be so hung as to require no center post in the opening for the doors to close against. 14. Lighting. Required stairways, hallways and other means of exit, including exterior open spaces to or through which exits lead, shall be kept adequately lighted at all times that the building served thereby is occupied. SECTION 13A. FIREPROOF, SEMIFIREPROOF AND TIMBER CONSTRUCTION Fireproof, semifireproof and heavy timber construction shall conform to generally accepted good practice. The 1960-61 Edition of the National Building Code recommended by the National Board of Fire Underwriters shall be deemed the generally accepted good practice for these types of construction. SECTION 13B. ORDINARY CONSTRUCTION. 1. Defini_tion. Ordinary construction, as applied to buildings, means tb:.t is which exterior walls and bearing walls are of masonry or of reinforced concrete, and in which the structural members, l.acluding columns, floor and roof construction, are wholly or party of wood of smaller dimensions than required for heavy timber construction or of steel or iron not protected as required for st?mifire-proof construction. 2. Walls. (a) Exterior walls and all bearing walls shall be of masonry or reinforced concrete. (b) Exterior walls which are within 3 feet of a lot line along an adjoining area which is or may be built upon or Page - •11 - which are within 6 feet of another building of other than fire- proof or semifireproof construction on the same lot, shall have a fire resistance rating of not less than 3 hours; except that where the total area of the buildings does not exceed la times the allowable area for any one of the buildings considered such fire resistance rating shall not be required. 3 Beame,girders and joists. (a) Wooden beams and joists, except headers and tail joists, and except for bearings at joints limited within the allowable stresses provided in this code, shall have bearings of at least 3 inches in length. (b) Wooden trimmers, headers, and tail joists over 6 feet in length, unless supported on walls or girders, shall be hung in approved metal stirrups or hangers. If wood girders are set flush with the floor joists, the joists shall rest in approved metal stirrups or hangers. The end of joists against the girders shall be securely nailed to the girders. (c) Except in the case of pitched roofs, wooden floor and roof joists having spans in excess of 8 feet shall be rigidly braced with continuous rows of bridging at intervals not exceeding 8 feet. (d) Joist shall be doubled under partitions which run over and paralled to the joists, or shall be designed for the load. (e) 'The ends of wooden beams and joists resting on masonry shall be cut to a bevel of 3 inches in their depth. (f) Wooden joists, beams and girders resting on opposite sides of a masonry wall shall be separated from one another by at least 6 inches of solid masonry. (g) When a wooden girder rests on masonry an air space of a inch shall be provided on the sides and end of such girder for ventilation, and each wallbearing end of a girder shall be cut on a bevel. 4: Anchorages.:. (a) All trimmers and at least one beam or joist in every six feet resting on masonry walls, shall be secured to such walls by approved metal anchors attached at or hear the bottom in a manner to be self -releasing: Each end of a trimmer, beam or joist that is supported by a girder, shall be secured or tied in an approved manner to 814n girder or to a trimmer, beam of joist correspondingly supportrom the opposite side of such girder. Anchors and ties shall be so arranged as to form continuous ties between opposite masonry walls. (b) Where floor or roof joists or beams run parallel to masonry walls such walls shall be secured to 4 or more joists of the floor or roof construction by approved metal anchors at maximum intervals of 8 feet for dwellings, and 6 feet in other buildings. (c) Wall plates and roof construction shall be anchored to the walls at least every 6 feet. (d) Wooden girders shall be anchored to the walls and fastened to each other with suitable steel straps placed near the bottom of the girder. 5. Load -bearing partitions. (a) Load -bearing partitions shall be the equivalent of 2 x LF inch studs, nominal dimensions, spaced not to exceed 16 inches or centers with the larger dimension perpendicular to the wall. All openings shall have studs doubled on each side and if more than 3 feet and 6 inches wide they shall be trussed over or shall have lintels of sufficient size to carry the load. (b) Load -bearing stud partitions shall have top plates not smaller than double 2 x Lj. inch nominal dimensions, and shall be set over girders or other partitions below, with the space between the ceiling and the floor above firestopped with solid 2-inch, nominal thickness plank, or with non- combustible material. 6. Wooden Columns. (a) Wooden columns in the several stories of a building, shall be set directly above one another, on top of the column below. (b) The loads on wooden column shall be transmitted to the columns below through reinforced concrete or metal caps with brackets, or through metal caps and bases with pintle Page - 12 - connections or other approved column connections; provided that wooden bolsters may be used to support roof girders. (c) Wooden columns shall not rest directly on floor joists. (d) When supported by masonry, suitable stone or metal bases shall be set between the column and the masonry. 7. Firestopping two story. (a) When the walls are furred, the space created by the furring shall be firestopped with noncombustible materials at floors, ceilings and roofs. The firestopping shall be the full thickness of the furring and extended from the ceiling to the underside of the flooring or roof. (b) When joists run parallel to the wall the space between the wall and nearest joist shall be not less than 1 inch and shall be solidly filled with masonry or approved noncombustible material. (c) Interior stud partitions shall be firestopped at the floors and ceiling of each story by a 2-inch nominal dimen- sion, wood plate, the width of the stud, or the equivalent. (d) Joists shall be firestopped at the ends and over supports for ;the full depth of the joists with noncombustible material or with wood not less than 2 inches in thickness, nominal dimension. (e) No firestopping shall be covered or concealed until inspected by the building inspector. 8. Bay windows and show windows. Bay windows and show windows that extend beyond exterior walls shall be constructed of noncombustible materials; except that show windows that do not extend above the secondfloor level and bay windows on dwellings may be constructed of wood. 9. Mansard roofs. Mansard or other slanting roofs having a pitch of more than 60 degrees from the horizontal, hereafter placed on a building over 40 feet in height, shall be of fireproof construction or semifireproof construction. 10. Draft stops in attic spaces. Attic spaces shall be divided into areas of 5,000 square feet or less by tight draft stops; these shall be of 2 thicknesses of 1-inch lumber with joints broken or the equivalent, with access doors of similar construction. SECTION 14. NONCOMBUSTIBLE CONSTRUCTION. 1. Definition. Noncombustible construction, as applies to buildings, means that in which all structural members, including floors, roofs and their supports, are of steel, iron, concrete, or of other noncombustible materials, and in which the exterior walls are of noncombustible construction having a fire resistance rating of not less than two hours. 2. Walls. Exterior enclosure walls shall provide a durable and stable weatherproof exterior. iron • Structural members. All structural members shall be of steel, reinforced concrete, or of other approved non- combustible materials. 4. Partitions. (a) If combustible material enters into the con- struction of partitions, they shall be built to have a fire resistance rating of not less than one hour; but this shall not prohibit the use of wooden doors, door casings, frames, jambs and bucks, window and transom frames and casings, unless the partitions are required to be fire partitions. (b) Nothing in this section shall prevent the erection of temporary partitions of wood and glass or of metal and glass within the rooms or spaces occupied by a single tenant. (e) All permanent partions shall rest on noncombust- ible materials. SECTION 15. l'OOD FRAME CONSTRUCTION. 1. Definition. Wood frame construction, as applied to buildings, means that in which walls and interior construction are wholly or partly of wood. 2. Walls. (a) Framing for exterior walls shall be constructed to develop a strength and rigidity equivalent to wooden studding Page - - not less than 2 by 4 inches, nominal dimensions, spaded 16 inches on centers with the larger dimension.perpendicular to the wall, and braced with sheathing or diagonal bracing at the corner to secure the necessary rigidity; except that on one -,story buildings studs not over 10 feet in length may be spaced not to exoeed 24 inches on centers. (b) In buildings except private garages, ah exterior wall which in less than 3 feet distant from the lot line along an adjoining area which is or may be built upon shall be of noncombustible construction having a fire resistance rating of not less than two hours; except that the material of the weather surface may be similar to that of other exterior walls of the building. 3. Stucco. (a) Stucco shall consit of portland cement mortar or other approved mortar, on approved metal lath, or other approved backing. (b) Stucco shall be kept at least 8 inches above adjacent ground surfaces, with sills, coping and other.projeCting courses provided with drips. (c) Corrosion -resistant flashing, to prevent moisture from penetrating behing the stucco, shall be provided over wall openings and over projecting courses: L. Sills. Sills on outside perimeter walls shall be anchored to the foundation walls at intervals not exceeding 6 feet by anchors equivalent to bolts not less than a inch in diameter with proper washers, embedded at least 4 inches in the foundation. (a) In all buildings 20 feet or more ih width where joists run at right angles to the rafters, the rafters shall be tied to the ceiling joists with wood or metal ties nailed to the foot of alternation rafters and extending across 4 joists well nailed to each joist. (b) All joists shall be well lapped and hailed across the building to form ties between outside walls. 5. Beams, girders and joists shall conform to the requirements of Section 13-B, Paragraphs (a) to (d) inclusive. Where ledger or boards are used to support joists, such boards shall be not less than 1 x 2 inch, nominal dimensions, shall be cut into the studs and securely nailed with not less than 2 tenpenny nails to each stud, and the joists shall be spiked to the studs. 6. Load -bearing partitions shall conform to the require- ments of Section 13-B. 7. Wooden columns shall conform to the requirements of Section 13-B. 8. Firestopping. (a) Exterior walls of wood frame construction shall be properly firestopped at each floor level, at the top story ceiling level, at the roof level in the case of flat roofs. (b) Joists shall be firestopped at the ends and over supports for the full depth of the joists. (c) Interior stud partititions shall be firestopped at the floor and ceiling of each story by a 2-inch, nominal dimension, wood plat, the width of the stud, or the equivalent. (d) Firestopping shall be of noncombustible material or of wood not less than 2 inches in thickness, nominal dimension. No firestopping shall be covered or concealed until inspected by the building inspector. 9. Draft stops in attic spaces. Draft stops shall be provided in attic spaces as required by Section 13-B. SECTION 16. UNPROTECTED METAL CONSTRUCTION. Unprotected metal construction, as applied to buildings, means that in which the structural supports are unprotected metal and in which floorsand roofs are of noncombustible con- struction, and the exterior walls are of noncombustible con- struction having a fire resistance rating of less than 2 hours. SECTION 17. WORKMANSHIP AND MATERIALS. All building materials shall be of good quality. Work- manship in the fabrication, preparation and installation of material Page -14.- shall conform to generally accepted good practice. SECTION 18. DESIGN LOADS, STRESSES AND WIND PRESSURE. Commercial buildings or structures, including tanks, towers and signs, hereafter erected and all new construction in the alteration of heretofore erected buildings or structures shall be designed and constructed for live and dead loads and wind pressures in accordance with the National Building Code, 19L9 Edition, recommended by the National Board of Fire Under- writers, and with resulting stresses not in excess of those permitted by said code. SECTION 19, MASONRY. 1. Construction. (a) All masonry shall be protected against freezing for at least 48 hours after being placed. Unless adequate precautions against freezing are taken, no masonry shall be built when the temperature is below 32 degrees Fahrenheit on rising tem- perature or below 40 degrees on a falling temperature at the point where the work is in progress. No frozen materials shall be built upon. (b) Except when carried independently by girders at each floor, no wall shall be built upon more than 25 feet in height in advance of other walls of the building. (c) Masonry walls that meet or intersect shall be adequately bonded or anchored. Piers having less than !4. square feet of cross -sectional area when located at an intersection with a wall shall be bonded into and built as part of that wall. (d) Except for window -paneled backs and permissible chases and recesses, walls shall not Ian in thickness between their later lateral supports. When a change in thickness, due to minimum thickness requirements, occurs between floor levels, the greater thickness shall be carried up to the higher floor level. (e) Isolated piers or posts on the interior of build- ings shall not be built of stone. The unsupported height of piers shall not exceed 10 times their least dimension. Hollow masonry units shall not be used for isolated piers to support beams and girders unless solidly filled with concrete or Type A mortar in which case the allowable load may be increased 25 per cent. (f) Door and window openings in walls shall be spanned by well buttressed arches, or by lintels having bearings proportioned to their loads but not less than 4 inches. (g) No masonry, except for interior partitions, shall be supported on wooden girders or other form of wood construction. (h) No timber, other than nailing blocks not exceeding 2 by 4 by 8 inches in size, shall be placed in masonry walls; except that in buildings of ordinary construction, timber esnd e1s chpenod n t over tiro inces1on tneo.wa the wall, an c are or cut to serve as centers -tor masonry arches; and with the further exception that timber members used for decorative purposes may be set against the masonry, or may be set into the masonry where the walls exceeds 8 inches in thickness. (i) During erection, walls shall be adequately braced and arches temporarily supported. 2. Mortar. (a) Mortar used in masonry construction shall be proportioned in accordance with the following table: MORTAR PROPORTIONS Mortar Type Proportions by Volume Cement ord imedPu y agnampgaand loos ed ir. condition A 1 (Portland) 0 to 2 Not over 3 parts B 1 (Portland) 1 to 14 Not over 6 parts B 1 (Masonry 0 Not over 3 parts Type II*) Page - 15 - C C D 1 (Portland) 1 (Masonry) Type 1* 0 to 1 (Portland) 2 to 22 Not over 9 parts 0 Not over 3 parts 1 to 14 Not over 3 parts *As defined in Federal Specification SS-C-181 B, Masonry Cement. (b) Type of mortar required. Masonry shall be laid in Type A, Type B or Type C mortar, except as follows: Type A Mortar shall be used in foundation walls of hollow masonry units, and in nominal 10-inch cavity walls. Type A or Type B. Mortar shall be used in footing, foundations walls of solid masonry units, isolated piers, load bearing or exterior walls of hollow masonry units, hollow walls and cavity walls exceeding 10-inch nominal thickness. Type D mortar may be used in solid masonry walls, other than parapet walls or rubble stone walls, not in contact with the wall and not }ess than 12 inches thick nor more than 35 feet in, height, provided the walls are laterally supported at intervals not exceeding 12 times the wall thickness. Gypsum partition tile and block shall be laid in gypsum mortar. Nonbearing partitions and fireproofing of structu- ral clay tile may be laid in gypsum mortar. Fire brick shall be laid in fire clay mortar. 3. Solid Masonry walls, except stone walls. (a) Thickness of Bearing Walls. (1) Except as otherwise provided in paragraph (2) to (6) below, the minimum thickness of solid masonry bearing walls other than fire walls and party walls shall be not less than 12 inches for the uppermost 35 feet of their height, and shall be increased 4 inches for each successive 35 feet or fraction there- of measured downward from the top of the wall. (2) Where solid masonry bearing walls are stiffened at distances not greater than 12 feet apart by cross walls, or by internal or external offsets or returns at least.2 feet -deep, or 12 feet vertically by reinforced concrete floors or roof, they may be 12 inches thick for the uppermost 70 feet, measured downward from the top of the wall, and shall be increased LE inches in thickness for each successive 70 feet or fraction therof. (3) In residential buildings not more than three stories in height, solid masonry bearing walls may be 8 inches thick when not over 35 feet in height. Walls in one-story dwellings and one-story private garage shay be 6 inches thick when not over 9 feet in height, except that the height to the peak of a gable may be 15 feet. (LF) outside solid masonry bearing walls of business buildings and storage buildings not more than one story high, may be bin thick for areas not in excess of 750 square feet. (5) outside of the fire limits solid masonry bearing walls, 8 inches thick, may be used for buildings not exceeding 30 feet nor 2 stories in height, the walls of which, under this code, could be of wood frame construction; provided they do not exceed 50 feet in length between cross walls, piers, or buttresses. (6) Solid masonry bearing walls above roof level, 12 feet or less in height, enclosing penthouses or roof structures may be 8 inches thick and may be considered as neither increasing the height nor requiring any increase in the thickness of the wall below, provided the requirements for allowable stres- ses are met. (b) Thickness of Non -bearing Exterior walls. The thickness of nonbearing exterior walls,except fire walls and part walls, shall be not less than 3 inches for the uppermost 15 feet, and shall increase 4 inches in thickness for each suc- cessive 35 feet or fraction thereof measured downward from the top of the wall. (c) Lateral Support. Solid masonry walls shall be supported at right angles to the wall face at intervals not exceeding 20 times the nominal wall thickness if laid in Type A, B. or 0 mortar, and not exceeding 12 times the nominal wall thickness if laid in Type D mortar. Such lateral mortar shall conform to subsection 10 of this section. Page - 18 - (d) Bond. The facing and backing of solid masonry bearing walls shall be bonded so that not less than 4 per cent of the wall surface is composed of full length headers. The distance between adjacent full length headers shall not exceed 24 inches either vertically or horizontally in solid brick walls more than 12 inches thick the inner joints of header courses shall be covered with another header course which shall break joints with the course below. The facing and backing of solid masonry nonbearing walls shall be bonded as required above for bearing walls or shall be bonded with corrosion -resistant metal ties spaced not farther apart than 18 inches vertically and 24 inches horizontally. (e) Other requirements. (1) Under -burned clay bricks shall not be used in any part of a building or structure where exposed to the weather, nor in isolated piers nor in such part of a bearing wall above which the wall extends more than 40 feet. (2 e Olay or shale brick laid in Type A or Type B mortar shall wet immediately before being laid, except that very hard or vierfied brick need not be wetted. (3) Horizontal and vertical joints in brick masonry shall be filled with mortar. (4) Except in dwellings interior bearing walls that are less than 12 inches in thickness and support wooden floor or roof joists, shall be corbeled not less than 3 inches to receive such joists, unless approved metal joist hangers are used. 4. Stone Walls_ _ (a) 7h.ickness. (1) The minum thickness of walls of stone ashlar shall be not less than that required for solid masonry walls in subsection 3 of this section. (2) Rubble stone walls shall be 4 inches thicker than is required for solid masonry walls in subsection 3 of this section, but shall not be less than 16 inches thick, and shall not exceed 40 feet in height. (b) Lateral Support. Stone walls shall conform to the requirements for lateral support of other solid masonry walls in subsection 3 of this section. (c) Bond. (1) In ashlar masonry, bond stones uniformly dis- tributed shall be provided to the extent of not less than 10 per cent of the area and having not less than 4 inches of bond into the backing masonry. (2) Rubble stone masonry 24 inches or less in thick- ness shall have bond stones with a maximum spacing of 3 feet vertically and horizontally, and if the masonry is of greater thickness than 24 inches shall have one bond stone for each 6 square feet of wall surface on both sides and no header stone shall be less than 12 inches long measured at right angles to the face of the masonry. (d) Natural Beds. All stones showing pronounced . • cleavage shall be laid on their natural bed, except for cornices and other projecting members which shall have the grain or bedding planes vertical and at right angles to the face of the masonry. 5. Walls of hollow masonry units. (a)—1h.+ckuess and height. (1) The mi.n±mum thickness of walls of hollow masonry units shall be not less than that required for solid masonry walls in subsection 3 of this section. (2) Walls of hollow masonry units shall not exceed 50 feet in height. (b) Lateral support. Walls of hollow masonry units shall be supported at right angles to the wall face at intervals not exceeding 18 times the nominal wall thickness. Such lateral support shall conform to subsection 10 of this section. (c) Bond. (1) Hollow masonry units shall have full mortar cover- age of the face shells in both the horizontal and vertical joints. (2) Where two or more hollow units are used to make up the thickness of a wall, the inner and outer courses shall be bonded at vertical intervals, not exceeding 3 feet, by lapping Page - 17 - at least 4 inches over the unit below or by lapping with units at least 50 per cent greater in thickness than the unit below at vertical intervals not exceeding 17 inches. (3) Brick facing or lining (which does not include veneering)when used in hollow block walls shall be bonded to the backing in accordance with paragraph (d) of subsection 3 of this section. (4) Where walls of hollowmasonry units are decreased in thickness, a course of solid masonry shall be interposed between the wall below and the thinner wall above, or the hollow units in the top course of the thicker wall shall be filled solidly with mortar or masonry, and shall have horizontal masonry steel reinforement sized .for corresponding wall thickness every forth course, or not less than 3 feet vertical spacing, throughout the full length of the masonry wall. (d) Be^ring: In walls and piers of hollow masonry units, suitable provisions shall be made for the proper bearing at the ends of all beams and at points of load concentration. 6. C^vt ty Walls and Hollow Walls. (a) Height anJ 1, i ckness . (1) Cavity walls and hollow walls shall not exceed 35 feet in height. Cavity walls, exclusive of the cavity, and hollow walls shall be not less in thickness than required for solid masonry walls in subsection 3 of this section. (2) In cavity walls neither the facing nor the backing shall be less than 3 3/4 inches in nominal thickness and the cavity shall be not less than 2 inches nor more than 3 inches in width. (b) Lateral support. Cavity walls shall be supported at right angles to the wall face at intervals not exceeding 14 times, and hollow walls at intervals not exceeding 18 times the nominal wall thickness. Such lateral support shall conform to subsection 10 to this section. (c) Bond (1) In hollow walls the parts of same shall be connected by bonds of brick, stone cr material of wall, placed not more than 24 inches apart in either direction; but the parts shall not be deemed to act together in the support of loads unless such bonds are of a size and design to fully develop the strength of either part. (2) In cavity walls the facing and backing shall be securely tied together with suitable bonding ties of adequate strength. A 3/16 inch diameter steel rod or metal tie or equivalent stiffness coated with a noncorroding metal or other approved protective coating shall be used for each 3 square feet of wall surface. where hollow masonry units are laid with the cells vertical, rectangular ties shall be used; in other wa11n the ends of ties shall be bent to 90 degree angles to provide hooks not less than 2 inches long. Ties shall be embedded in horizontal points of facing and backing. Additional bonding ties shall be provided at all openings, spaced not more than 3 feet apart around the perimeter and within 1.2 inches of the opening. Cavity walls of plain concrete shall be reinforced as provided for solid walls or plain concrete in subsection 9 of this section. (d) Bearing. (1) In hollow walls or cavity walls suitable provision shall be made at each line of floor beams and wherever load concentrations occur, to insure proper bearing. (2) When ca ity walls or hollow walls in which the c814 .8 ftpoil o prtits aro la.i.d vertical, are decreased in .thickness, /top course oT thicker wall shall be filled solidly with mortar or masonry or the exposed openings in such top course shall be covered with slab of hard burned tile or concrete at least one inch in thickness or the openings may be stopped in some other approved manner. (e) Drainage. In cavity walls the cavity shall be keptclear of mortar droppings during construction. Approved flashing shall be installed and adequate drainage provided to keep dampness away from the backing. 7. Faced Wails. (a)-'i�I;x'teriaC Materials used for facing shall be not less than 22 inches thick, and in no case less in thickness than 1/8 the height of the unit. (b) Allowable stresses. Where,bonded to the backing as prescribed below the full dross section of both the facing and the backing may be considered in counting the stresses. (c) Thickness. Faced walls shall be not less in thickness than is required for masonry walls of either of the types forming the facing and the backing. Where bonded to the backing as prescribed below, the facing may be considered a part of the wall thickness. (d) Bond. (1) Brick facing shall be bonded to the backing as prescribed for solid masonry walls in subsection 3 (d) of this section. (2).. Ashlar facing of either natural or cast stone shall have at least 20 per cent of the superficial area extending not less than 4 inches into the backing to form bond stones, which shall be uniformly distributed throughout the wall. (3) When walls of hollow masonry units are faced with hollow units, the facing units shall be bonded to the backing as required for walls of hollow masonry units in subsection 5 (c) of this section. 8. Attachment of stone facing. Every projecting stone, and except when alternate courses are full bond courses, every stone not a bond stone shall be securely anchored to the backing with corrosion resistant metal anchors with a cross section of not less than 0.2 square inch. There shall be at least 1 anchor to each stone and not less than 2 anchors for each stone more than 2 feet in length and 3 square feet in super- ficial area. Facing stones not over 12 square feet in area shall have at least 1 anchor to each 4 square feet of superficial face area.' 9. Solid. Walls of plain concrete. (a) Thickness. The minimum thickness of walls of plain concrete may be 2 inches less than that required for solid masonry walls, but not less than 8 inches, except that 6 inch walls may be used where specifically permitted by subsection 3 (a) (3) of this section. (b) Lateral support. Solid walls of plain concrete shall be supported at right angles to the wall face at intervals not exceeding 20 times the nominal wall thickness. Such lateral support shall conform to subsection 30 of this section. (c) Reinforcement around `openings. Reinforcement symmetrically disposed in the thickness of the wall shall be placed not less than 1 inch above and 2 inches below openings and extend not less than 24 inches each side of each opening or be of equivalent length with hooks. The reinforcement both above and below shall consist of one 5/8 inch round rod for each 6 inches in wall thickness or fraction thereof. 10. Lateral Support. The lateral support required by subsection 3, 4, 5, 6 and 9 of this section shall be either vertical or horizontal. It may be obtained by cross walls, piers, or buttress, when the limiting distance is measured hori- zontally, or by floors and roofs when the limiting distance is measured vertically. Sufficient bonding or anchorage shall be provided between the walls and the supports to resist the assumed wind force, acting either inward or outward. Piers or buttress relied upon for lateral support shall have sufficient strength and stability to transfer the wind force, acting in either direction to the ground. When walls are dependent upon floors or roofs for their lateral support, provisions shall be made in the building to transfer the lateral forces to the ground. SECTION 20. REINFORCED CONCRETE (a) Concrete for reinforced concrete shall be capable of developing a strength of 2500 p. s. i. at the end of 28 days. (b) The National Building Cod:, 1949 Edition, recommended by the National Board of Fire Underwriters, shall be deemed to be the generally accepted good practice in re- inforced concrete construction. SECTION 21. FIRE WALLS AND PARTY WALLS. Page - 13 - 1. Construction. (a) Fire walls and party walls of marsonry shall be laid in Type A or Type B mortar. (b) Fire walls and party walls shall be constructed •of solid masonry units, or of hollow masonry units faced on each side with brick, or of reinforced concrete, (c) Where structural members project into hollow masonry units the hollow space shall be filled with noncombustible material the full thickness of the wall and 4 inches or more above between and below each member. 2. Thickness of solid masonry walls except panel walls, (a) For business buildings and storage buildings, fire walls and party walls of solid masonry units shall be not less than 16 inches thick for the uppermost 50 feet and increase 4 inches in thickness for each additional 35 feet or fraction thereof measured downward from the top of the wall; except that where the walls are non -bearing, or where beams or girders are supported on the wall be approved metal hangers and do not enter the wall the minimum thickness may be 16 inches for the upper- most 70 feet. (b) For other buildings, fire walls and party walls of solid masonry units shall be not less than 12 inches thick for the uppermost 35 feet and increase 4 inches in thickness for each additional 35 feet or fraction thereof measured down- ward from the top of the wall. 3. Thickness of brick -faced hollow masonry walls. Fire walls and partywalls of hollow masonry units faced on each side with a least 4 inches of brick shall have a total thickness including the facing not less than 4 inches greater than specified in subsection 2 above for solid masonry walls. 4. Thickness of reinforced concrete walls except panel walls. (a) For business buildings and storage buildings, fire walls and party walls of reinforced concrette shall be not less than 11 inches thick for the uppermost 35 feet and increase 2 inches in thickness for each successive 35 feet or fraction thereof measured downward from the top of the wall. (b) For other buildings, fire walls and party walls of reinforced concrete shall be not less than 9 inches thick for the uppermost 35 feet and increase 2 inches in thickness for each successive 35 feet or fraction thereof measured downward from the top of the wall. 5. Exception to thickness requirements for panel walls. Where fire walls or party walls are constructed as panel walls in a framework of columns and girders protected as required for fireproof construction and no panel has a height between supports greater than 12 feet, they may be of solid masonry not less than 12 inches thick or of reinforced concrete not less than 8 inches thick. 6. To be carried to or above the roof. Fire walls and party walls shall extend at least 3 feet above the roof; except where the roof is of fireproof or semifireproof construct- ion in which case the fire walls and party walls shall be carried up tightly against the underside of the roof slabs. 7. Size and protection of openings. (a) Except in sprinkiered buildings, no opening in a fire wall shall exceed 120 square feet in area with no dimen- sion greater than 12 feet, and the aggregate width of all openings at any level shall not exceed 25 per cent of the length of the will. (b) Every opening in a required fire wall shall be protected on each side of the wall with an approved automatic or self -closing fire door; provided that when a fire wall serves also as a horizontal exit it shall have no openings other than door openings not exceeding 48 square feet in area, and one of the fire doors at each opening shall be a self -closing fire door. SECTION 22. PARAPETS (a) Except as listed below, parapets shall be provided on all fire walls, party walls, and exterior walls of masonry or reinforced concrete. Parapets are not required on Page - 20 (1) Walls connecting with roofs or fireproof con- struction or semifireproof construction; (2) A wall of a building the roof of which is at least three feet lower than the roof of, or any opening in, an adjacent building wall; (3) Walls facing on a street having a width of 30 feet or more; (Lh) Walls of a building which is 30 feet or more distant in all directions from property lines and other buildings on the same property; (5) Walls of a building which is 30 feet or more distant in all directions from property lines but less than 30 feet distant to one or more building on the same property, where the total area of the buildings within 30 feet of each other does not exceed 12 times the allowable area for any one of the building considered; (6) Walls of a detached dwelling, or of a building not exceeding 1,000 square feet in area; (7) Walls of a building where the roof has an angle of more than 20 degrees with the horizontal. (b) In dwellings and in buildings in which 8 inch walls are permitted, such parapets shall not be less than 8 inches thick and carried at least two feet above the roof. (c) In all other buildings such parapets shall be not less than 12 inches thick and carried not less than 3 feet above the roof. (d) Parapets shall be properly coped with non- combustible, weatherproof material and flashed with the flashing extending through the parapet wall under the coping. All corners of all parapet walls shall be reinforced with at least one 4 inch round bar in every third joint, continuous around the corner and extending into the masonry at least 3 feet from the corner. SECTION 23 FIRE PARTITIONS I Construction (a) Fire partitions shall have fire resistance rating of at least two hours. They shall be constructed of masonry or reinforced concrete or other approved form on construction of noncombustible materials. Fire partitions used for load bearirc shall conform to the requirements for bearing walls in sections '21 and 22, in addition to meeting the requirements of this section. (b) Fire partitions shall be supported in each story on construction having a fire resistance rating of not less than 2 hours; provided that when they also are load bearing, the supporting construction shall have a fire resistance rating of not less than 4 hours in case the building is of fireproof construction or semifireproof construction, and not less than 3 hours in case of other construction.. (c) The maximum unsupported height of a fire part- ition shall not exceed 18 times its total thickness unless suitably reinforced and anchored at floor and ceiling or sub- stantially secured to vertical supports at intervals of not over 18 times the thickness. (d) Fire partitions shall be deemed continuous, even through the several parts are not directly over oneanother insuccessive stories if the intervening parts of the floors at the levels where offsets occur, and unpierced and of fireproof construction or semifireproof construction and all parts not supported directly on the foundations are carried on fireproof construction. 2. Openings. (a) Required fire partitions shall have no.. openings other than required door openings, or properly protected duct openings. (b) Each opening in a required fire partition shall be equipped with an approved fire door set in approved door frame. (c) Each opening in a fire partition serving as a horizontal exit shall be protected by an approved self -closing fire door. Page - 21 - SECTION 24. PROTECTION OF EXTERIOR OPENINGS Every building, except dwellings, churches, buildings of wood frame construction and of unprotected metal construc- tion, and open air parking garages shall have approved fire windows or other approved protectives, in every opening in the exterior walls when each opening faces on a street and is less than 30 feet from the opposite building line, or when such opening is less than 30 feet distant in a direct unobstructed line from an opening in another building, or when such opening is above and not more than 30 feet distant from any part of a neighboring roof or combustible construction, or any roof having openings within this distance; provided that such pro- tection shall not be required for show windows facing on a street which does not extend above the first full story above grade, and provided further that such protection shall not be required when the opening to be protected and the opening against which it is to be protected are situated in walls in the same plane or in parallel planes and are facing the same directions. SECTION 25. SHAFTS 1. Protection required. (a) Every series of openings above one another in two°more successive floors, or floors and roof, hereafter placed or constructed in a building or hereafter enlarged or altered to change the use of the shaft, shall be so protected as to prevent fire in any story from communicating to any other story; provided that in buildings of heavy timber construction there shall be no floor opening that is not protected as prescribed in this section or in some other approved manner. (b) The provisions of this section shall apply to all shafts used for ventilation, light, elevator, pipes, or other purpose, except stairways, airducts, incinerator chutes, flues, shafts in buildings of wood frame construction, shafts in dwellings, and ramps in garages exempted by Section 32-6, 2. Shaft enclosures. The enclosing walls of shafts in residence buildings of ordinary construction or noncombustible construction or unprotected metal construction shall have a fire resistance rating of not less than 1 hour. The enclosing walls of shafts in other buildings shall be of noncombustible construction having a fire resistance rating of not less than 2 hours. 3. Openings. Shaft enclosures shall have no openings other than those necessary for the purpose of the shaft; provided that in elevator shafts there shall be at least one door in every 30 feet of height of such shaft. Such openings shall be protected with approved fire doors, approved fire shutters or approved fire windows. L... Enclosure at top. (a) Shaft enclosure extending through the roof which are to be enclosed at the top, shall be provided with a skylight of at least 10 per cent of the arelof the shaft in the top story and glazed with plain glass 1/8 inch in thickness; provided that the skylight may be replaced by a window of plain glass of equivalent area in the side of the shaft if the sill of such window is not less than 2 feet above the roof and the window does not face a let line within 10 feet, or may be replaced by approved means of ventilation. (n) A shaft that does not extend through the roof shall have the top enclosed with a form of construction having a fire resistance rating equal to that of the walls of the shaft. 5. Enclosure at bottom. A shaft that does not extend to the bottm of the building shall be enclosed at its lowest point with a floor con struction of the same type as that required for the lowest floor to or through which it passes, but such shaft floor construction shall have a fire resistance rating of not less than one hour. 6. Elevator machinery compartment. Compartments containing machinery for operating elevators shall be separated from the elevator shafts by noncombustible construction having page - 22 - a fire resistan4e rating of not less than 2 hours, with tor - openings equipped with approved fire doors. 7. Number of elevators in shaft. Nat more than 3 elevators shall' be laced hereafter on one shaft. SECTION 26. ROOFING (a) Every roof hereafer placed on a building shall be covered w' a ed roofing of brick, concrete, tile, slate, metal ¥bet PS tepared asphalt asbestos -felt shingle, or of built-up roofing finished with asphalt, slag or gravel, or other approved material. (b) Except where roofing is of a character per- mitting attachment direct to frame work, it shall be applied to a solid or closely fitted deck or wood strips. (c) Roofingswhich are listed as Class A or B roof covering materials by Underwriters" Laboratories, Inc., shall be accepted as meeting the requirements of this section. (d) Roofingswhich are listed as Class C, Roof covering material by Underwriters; Laboratories, Inc., shall be accepted as Meeting the requirements of this section on buildings as follows: (1) Dwellings (0) Buildings of Wood frame construction. (3) Buildings located outside the fire limits which do not' exceed 2 stories or 30 feet in height, or 2500 sq. ft. in area, and are not occupied as stores, factories or warehouses. '(ti-) Buildings which under this code could be of wood frame construction. (e) The use of cork, fiber board or other approved insulation is permitted -on top of the roof deck pro- vided such insulation is covered with an approved type of fire resistive roof covering applied directly thereto. (f) No roofing on an existing roof shall be removed or repaired to a greater extent than one -tenth of the roof surface, except in conformity with the requirements of this section. (g) Outside the fire limits, dwellings, private garages and barnes, separated by at least six feet from the other buildings may be roofed with approved vertical grain or edgegrain wooden shingles. The combined thickness of each five shingles measured at the butts shall be not less than two inches. The exposure of such wooden shingles to the weather shall not exceed, on roofs greater than one-third pitch, five inches for sixteen -inch shingles, five and one-half inches for eighteeninch shingles, and seven and one-half inches for twenty-four inch shingles; nor, on roofs with less than• one- third pitch, four inches for sixteen -inch. shingles, and six and one-half inches for twenty-four inch shingles. Such shingles shall be firmly nailed to the roof deck with non -cor- rodible and rust resistive nails according to accepted good practice. Unless otherwise specified by ordinance or duly promulgated rules, the Commercial Standard Or Wood Shingles, CS 31-38 of the U. S. Department of Commerce, shall be accepted as means of establishing the grade of shingles. SECTION 27 SKYLIGHTS. (a) Skylights placed over shafts, vent shafts and stair enclosures shall be glazed with plain glass not more than 1/8 of an inch in thickness. (b) Skylights other than as specified above, which are inclined less than 60 degrees from the horizontal, hereafer placed on a building shall have the sashes and frames thereof constructed of metal and glazed with wired glass; except that skylights in foundries or buildings where acid fumes are present, may be of wood by special permission of the building official. (c) Every skylight in..which plain glass is uded shall be protected by a substantial wire screen with wire not lighter than number 12 guage and having a mesh not less than 3/4 of an inch nor larger than 1 inch, placed not less than 4 inches nor more than 10 inches above the glazed portion of all Page - 23 - points, such screen shall extend beyond the glazing on all a des a distance not less than the height of the screen above the glaz- ing. (b) No chimney shall be corbeled from a wall more than 6 inches; nor shall a chimney be corbeled from a wall which is less than 12 inches in thickness unless it projects equally on each side of the wall; provided that in the second story of 2 story dwellings corbelling of chimneys on the exterior of the enclosing walls may equal the wall thick- ness. In every case the corbel shall not exceed one inch projection for each course of brick projected. (c) No change in the size or shape of a chimney, where the chimney passes through the roof, shall be made within a distance of 6 inches above or below the roof joists or rafters. (d) When a skylight is located over a stairway, public hallway or a place of assembly, a similar screen shall also be placed below the skylight, unless there is an intermediate ceiling light. SECTION 28. BASEMENT CEILINGS In buildings except dwellings and one-story buildings Outside of the fire limits, the ceiling over basements shall be fire retardant ceilings unless such basements are sprinklered. SECTION 29. CHIMNEYS, FLUES AND VENTS. 1. Flue connections required. Every heating appa- ratus or heat producing appliance requiring a flue connection shall be connected with a flue conforming to the provisions of this section or of section 32. This shall not include electric appliances, except as specifically required in section 32, nor oil fired appliances especially designed for use with- out flue connection. 2. Use of nonconforming flues. Flues not conforming to the requirements of this section for chimneys, not with generally accepted good practice for metal smoke- stacks, nor with section 32, vents for gas appliances, shall not be used unless listed by Underwriters' Laboratories, Inc. and installed in full compliance with the listing and the manufacturer's instructions, and such use is approved by the building official. 3. Construction. (a) Chimneys shall extend at least 4 feet above the highest point where they pass through the roof of the building and at least 2 feet higher than any ridge within 10 feet of such chimney. 4. Chimneys for heating appliances, low heat industrial appliances and portable type incinerators. a) Chimneys for fireplaces, chimneys for incinerators of non -portable type, shall be constructed of solid masonry units or of reinforced concrete. The walls shall be properly bonded or tied with corrosion resistant metal anchors. In dwellings and buildings of like heating requirements the thickness of the Chimney walls shall be not less than 4 inches. In other buildins the thickness shall be not less than 8 inches, except that rubble stone masonry shall be not less than 12 inches thick. (b) Every such chimney hereafter erected or altered shall be lined with a:flue• lining cooferming'tohequire- ments below: (c) Flue linings shall be made of fire clay or other refractory clay which will withstand the action of flue gases and resist without softening or cracking, the temperatures to which they will be subjected, but not less than 2,000 degrees Fahrenheit, or of cast iron of approved quality, form and construction. (d) Required clay flue linings shall be not less than 5/8 of an inch thick for the smaller flues and increasing in thickness for the larger flues. (e) Flue linings shall be installed ahead of the construction of the chimney as it is carried.up, carefully bedded one on the other in Type A, Type B or fire clay mortar with close fitting joints left smooth on the inside. Page - 24 - (f) Flue linings shall start from a point not less than 8 fiches below the intake, or, in the case of fireplaces, from the throat of the fireplace. They shall extend, as nearly vertically as possible, for the entire height of the chimney and be extended 4 inches above the top or cap of the chimney. (g) Cleanouts for flues or fireplaces shall be equipped with cast iron doors and frames arranged to remain tightly closed when not in use. (h) When two or more flues are contained in the same chimney, at least every third flue shall be separated by masonry at least 4 inches thick bonded into masonry wall of the chimney. Where flue linings are not so separated, the joints of adjacent flue linings shall be staggered at least 7 inches. 5. Use of flues. Chitneys or flues installed for the use of gas appliances but which are not suitable for solid or liquid fuels, shall be plainly and permanently labeled, "THIS FLUE IS FOR THE USE OF GAS BURNING APPLIANCES ONLY." The label shall be attached at a point near where the vent pipe enters the chimney, or with a type B gas vent used in place of a chimney, at a point near where the type B gas vent enters a wall, floor or ceiling. 6. Fireplaces. (a) The back and sides of fireplaces hereafter erected shall be of solid masonry or reinforced concrete, not less than 6 inches in thickness. A lining of fire brick at least 2 inches thick or other approved material shall be provided unless the thickness is 12 inches. (b) Wooden forms or centers used in the construction of that part of the supporting construction which is below the hearth of the fire place shall be removed when the hearth is completed. (c) Spaces between the chimney and joists, beams or girders and any, combustible materials shall be firestopped by billing with noncombustible material. SECTION 30. FLUES AND VENTS FOR GAS APPLIANCES. 1. Flue connections required. Every gas app- liance except those defined by N. G. U. as not requiring vents or flues, shall be connected to an effective flue extending to the out air and conforming to the provisions of subsection 2 of this section, if it is included in any of the following classifications, provided that such connections shall not be required for industrial appliances of such size or character that the absence of a connection does not consitute a hazard to the occupants: (a) Domestic appliances with input rating in excess of 50,000 Btu per hour, except domestic gas ranges. (b) Automatically controlled appliances with input rating in excess of 5,000 Btu per hour, except automatic instantaneous water heaters of the single faucet type, where the single faucent is attached to and made a part of the appliance. (c) Automatically controlled appliances with input rating less than 5,000 Btu per hour, unless equipped with an automatic device to prevent the s:excape of unburned gas at the main burner or burners. The term "automatically controlled appliances" used in paragraphs (b) and (c) refers to appliances to which the gas supply is automatically turned on and off in accordance with the demand for heat, but does not include appliances equipped with devices or controls governing the supply of gas to the main burner or burners which cannot automatically reduce the gas supply below 30 per cent of the input rating. (d) Appliances installed in the same room, which, if not vented would make the total input rating of unvented ggs appliances, not incuding domestic gas ranges, as great as 30 Btu per hour per cubic foot of room content. (e) Water heaters installed in bath rooms, bed rooms, or any occupied room normally kept closed. (f) Space heaters in sleepying quarters for use of transients. Page - 25 - (g) All house heating steam and hot water boilers and warm air furnaces in cluding floor furnaces. 2. Types of Flues. (a) Type A Flues: Chimneys or metal smokestacks. Type A flues are required fora (1) all incinerators: (2) all appliances which may be converted readily to the use of solid or liquid fuel; (3) all boilers and furnaces, other than attic furnaces, except where specific approval is obtained from the building official for the use of type B gas vents; (4) all other appliances except approved appliances which produce flue gas temperatures not in excess of 550 degrees F, at the outlet of the draft hood when burning gas at the manu- facturer's input rating. (b) Type B gas vents; Approved vent piping of non combustible,corrosion resistant material of adequate strength and heat insulating valve, and having bell and epigot or other acceptable joints. Type B gas vents shall be used only with approved gas appliances which are not required by paragraph (a) above to be vented to type A flues, except that they may be used when extended through an existing non -used chimney, whether the chimney is lined or not lined. (c) Type C gas vents; Vent pipes of sheet copper eiron earrogisRisf egt 'an �mattti l mUft, Se aaryabehuseall ooZx�vrunsdirectly from the space in which the appliance is located through a roof or exterior wall to the outer air. Such vent pipes shall not pass through any attic or concealed space nor through any floor. This shall not be construed as prohibiting the use of such vent pipes to vent attic furnaces installed in accord- ance with the provisions of this code. Installation with reference to clearance from combustible material and passage through wall or roof shall comply with the provisions of subsection 4 of this section. 3. Installation of type B gas vents. (a) Type B gas vents shall be made up with tight joints. (b) Type B gas vents shall be installed with a clearance to combustible material or construction whether plastered or unplastered, of not less than one inch, provided that for vents of floor furnaces such clearaace shall be not less than 3 inches for a distance of not less than 3 feet from the outlet of the draft hood, measured along the center line of the vent piping. (c) Suitable provision shall be made to prevent mechanical injury to type B gas vents where they extend through walls, floors or roofs. (d) Type B gas vents shall not be used with solid or liquid fuel burning appliances. 4. Installation of gas vents other than type B. (a) Gas appliance vent piping other than approved type B gas vents shall ...not ,_pass through any attic or concealed space nor through any combustible floor, and shall not pass through any combustible roof except;as specified in subsection 2 (c). Where passing through combustible roof in accordance with subsection 2 (c) they shall be garded at the point of passage as specified for passage through combustible walls partition in paragraph (b) below. Vent piping may extend through any existing chimney whether the chimney is lined or not. (b) Gas appliance vent piping other than approved type B gas vents shall not pass through combustible walls or partitions unless they are guarded at the point of passage (1) by metal ventilated thimbles not less than 6 inches larger in diameter than the pipe, or (2) by metal thimbles not less than 4 inches in diameter than the pipe with the annular space filled with mineral wool or other approved noncombustible insulating material; or in lieu of such protection all combustible material in the wall or partition shall be cut away from the vent pipe a sufficient distance to provide the clearance required from such vent pipe to combustible material - any material used to close up such opening shall be noncombustible. (e) Clearances from combustible material to gas appliance vent piping other than approved type B gas vents shall Page - 26 - be in accordance with standard practice for safe installation and use as required by section 31. 5. Flue mortar. All flue mortar for flues or vent pipes from gas burning appliances shall be aCid resisting. 6. Draft hoods. Every flue connected appliance except an incinerator unless its construction serves the same purpose, shall be equipped with an effective draft hood which either (1) has been approved as part of the appliances or (2) complies with nationally recognized standards for draft hoods. The draft hood shall be attached to the flue collar of the appliance or as near to the appliance as conditions permit and in a position for which it is designed with reference to horizontal and vertical planes. The draft hood shall be so located that the relief opening is not obstructed by any part of the appliance or adjacent construction. 7. Interconnection of vents. No vent pipe from a gas appliance shall be inter -connected with any other vent pipe, smoke pipe, or flue, unless such gas appliance is equipped with an automatic device to prevent the escape of unburned gas at the pain burner or burners. Where a gas appliance vent pipe is joined with a smoke pipe from an appliance burning some other type of fuel, for connection into a single flue opening they shall be joined by a Y fitting located as close as practicable to the chimney. With liquefied petroleum gases the automatic device to prevent the escape of unburned gas shall shut off the pilot light as well as the main burner or burners. SECTION 31. HEAT PRODUCING APPLIANCES, HEATING, VENTILATION, AIRCONDITIONING, BLOWER AND EXHAUST SYSTEMS. 1. Installation Standards. (Heat producing appliances and systems including incinerators) hereafter installed shall be installed in accordance with standard practices for safe installation and used without danger of overheating combustible material or construction. Ventilating, airconditioning, blower and exhaust systems hereafter installed shall be installed in accordance with standard practices for safe installation and use with all features presenting a possibility of starting or speading a fire safeguarded to a reasonable degree. Except as otherwise provided in rules duly promulgated by the building/inspector installation of such appliances and systems in accordance with the "Building Code Standards of the National Board of Fire Underwriters" for the installation of heat producing appliances, heating, ventilating, air conditioning, blower and exhaust systems." shall be deemed to be the standard practice for safe instal- lation and use. 2. Boiler and Furnace Rooms. (a) Heating boiler and furnace rooms in public buildings, institutional buildings, places of assembly, hotels, and multifamily houses shall be separated from other parts of the building by construction having a fire resistance ratingof not less than one hour. (b) Boiler rooms housing one more steam boilers carrying more than 15 pounds pressure with a rating of more than 10 boiler horsepower in other than factories, shall be separated from the rest of the building by noncombustible constructing having a fire resistance rating of not less then 2 hours, with door openings protected by approved fire doors. SECTION 32. GARAGES OTHER THAN DWELLING. 1. Garages combined with other occupancies. No garage than be attached to or form a part of a building of other occupancy except as provided in this section. 2. Garages not exceeding 600 square feet in area. (a) A garage not exceeding 600 square feet in area may be attached to or form a part of a residence building or a business building if separated from other occupancies Page - 27 - by walls, partitions and ceilings of materials to restrict the passage of gases, smoke and odor from the garage to other parts of the building. (b) Openings from the building into garage shall be restricted to a single doorway; such opening shall be provided with a metal, metal covered or solid wooden door of not less than 1-3/4 inches nominal thickness equipped with an approved self -closing device. (c) Floors shall be without pits or depressions. 3. Garages not exceeding 3,000 square feet in area. A garage not exceeding 3,000 square feet in area may be attached to or form a part of any building provided separation from other occupancies shall be by walls and floor and ceiling construction of at least one -hour fire resistance, and with all connecting openings provided with self -closing fire doors. Floors shall be without pits or depressions. 4. Garages exceeding 3,000 feet in area. (a) A garage exceeding 3,000 square feet in area may be located within or attached to a building occupied for any other purpose provided it is separated from such other oc- cupancy by masonry walls having a fire resistance rating of not less than 3 hours and by floors and ceilings of fire- proof construction or semifireproof construction. (b) Walls, floors and ceilings which effect such separation shall be continuous and unimpaired by openings of any kind; provided that door openings equipped with self - closing fire doors leading to salesrooms or offices that are operated in connection with such garages shall not be pro- hibited; and provided also that the use of elevators and stairways to other stories accessible only be vestibules or balconies, constructed and arranged as required for fire towers, shall be permitted. 5. Truck loading or unloading area. A truck loading or unloading area within a building occupied as a store shall be separated from other parts of the building b _:bhstin c- ta.on"havitrg-a?fi"re resistance rat.irgot nbt aess-than ogle hour, snalinaalsoe avavanrtesistanceurl in wi'tnotn essltnaLnnt dour. . eRLirreamps. ramps connecting ioors of garages, which are notconsidered as required exit ways under 13A, need not be enclosed in sprinklered garages, nor in open air parking garages. 7. Floors. Garage floors of other than earth construction which drain to sewers or storm drains shall be provided with an oil separator or trap. Where floor areas are extensive, a series of such drains shall be provided. The contents of oil separators or trap shall be collected at fre- requent intervals and removed from the premises. Floors in repair sections shall be concrete or other materials that may be readily cleaned. 8. Heating. (a) In garages exceeding 600 square feet in area, direct fired heating appliances, other than unit heaters located at least 8 feet above the floor, shall be located in a room used for no other purpose and cut off from the garage by noncombustible construction having a fire resistance rating of not less than 3 hours. Openings in the above mentioned cut-offs shall be restricted to those necessary for heating pipes and ducts. (b) Where gasoline dispensing equipment is located within a traveling distance of 25 feet from the entrace to the heater room, the floor of the heater room shall not be below grade level. SECTION 33. DISPOSAL OF WASTE DDRING CONSTRUCTION OPERATIONS. Waste material and rubbish shall not be stored nor allowed to accumulate within the building or in the immediate vicinity, and may be burned on job using ordinary safety pre- cautions. SECTION 34. ELEVATORS, MOVING STARIWAY AND AMUSE- MENT DEVICES. Page - 28 - 1. Elevators, moving stairways and amusement devices, hereafter erected, or installed, or hereafter altered shall be constructed, installed and maintained in accordance with rules duly promulgated by the building inspector or, in the absence of such rules, with "The American Standard Safety Code for Elevators, Dumbwaiters and Escalators" approved by the American Standards Association. 2. It shall be unlawful for the owner to operate or permit the operation or use of a passanger elevator, freight elevator, moving stairway or amusement device, hereafter ins- talled or constructed, until a certificate shall have been ob- tained from the building .iLispe,or. 3. The building iriepectorshall make or cause to be made an inspection of every passenger elevator at least once every three months, and of every freight elevator, moving stair- way and every amusement device at least once in every six months. SECTION 35. GAS PIPING. Piping for any and all types of gas used for light- ing or fuel purposes in building and structures shall be in- stalled to conform with generally accepted good practice. The "R" commended Good Practice Requirements for the Installation, Maintenance and use of Piping and Fittings for City Gas" and "Gas Systems for welding and Cutting" and Liquefied Petroleum Gases" of the National Board of Fire Underwriters shall be deemed to be the generally accepted good practice. SECTION 36. PLUMBING 1. General. Except as may be otherwise provided by law or ordinance, or rules duly promulgated by the buildingg inspectbr the plumbing and drainage system of a building or structure shall be installed in conformity with the "Recommended Minimum Requirements for Plumbing," of the Bureau of Standards, United States Department of Commerce. 2. Water Supply. (a) Every building in which people live, work or congregate shall be provided with ample water supply in- stalled and maintained in a satisfactory working condition. (b) In every multifamilty house there shall be in each apartment at least one kitchen sink with running water and water connection. The space underneath each sink shall be accessible. 3. Toilet facilities. (a) Except as otherwise prescribed by law or ordinance, in every existing building not already supplied and in every building hereafter erected, where there is continuous human occupancy or employment, there shall be a sufficient number of suitable and convenient water closets, propeak y connected with the drainage system. (b) In dwellings and multifamily houses there shall be at least one separate water closet within each apart- ment. L{.. Separate toilets. In buildings where more than one water closet is required, except in dwellings and multi- family houses, seperate water closets and toilet rooms shall be provided for the sexes. 5. Toilet rooms. (a) Water closets and urinals shall be placed in rooms or compartment which are devoted exclusively to toilet facilities. (b) In every water closet or urinal compartment hereafter constructed or installed, except in dwellings and multifamily houses , the entire floor and the sidewalls to a height of not less than 6 inches shall be be made waterproof with asphalt, cement, tile, marble, slate or other approved material im pervious to water. (c) The partitions enclosing toilet rooms shall be solid, except for the entrance door, and shall extend from the floor to the ceiling. Partitions separating water closets or urinals within a toilet room shall not extend to the ceiling but shall be so constructed as to permit circulation of air Page - 29 - throughout the toilet room. SECTION 37. SPRINKLER REQUIREMENTS. 1. Sprinklers required. In buildings hereafter erected, or altered to increase the area on height, approved automatic sprinkler equipment shall be installed and main- tained as specified in the following paragraphs. The areas specified shall be the area enclosed by exterior walls or fire walls or a combination thereof, except that in buildings or fireproof construction or semi fireproof construction the area shall be that enclosed by exterior walls, fire walls, or fire partitions or a combination thereof. (a) Buildings over 2 stories in height used for the manufacture, sale or storage of combustible goods or merchandise (not including garages) and exceeding in area 10,000 square feet when of fireproof construction or semifire- proof construction. (b) Buildings over 2 stores in height used for the manufacture, sale or storage of combustible goods or merchandise (not including garages) and exceeding in area 7,500 square feet when of types of construction other than fireproof construction and semtfireproof.:construction. (c) Buildings exceeding 2 stories in height or in excess of 2,000 square feet in area on any floor above the first or ground floor, hereafer erected or altered, so that suitable access, as defined below, to each story above the basement is not prbvided on at least one side of the building. Suitable access shall be deemed as requiring a usable opening through the wall at each story at least 32 inches wide, 48 inches high and with the sill not more than 32 inches above the floor; the opening shall be so spaced that there will be one opening for each 50 feet of frontage. (d) Garages exceeding 6 stories in height. (e) Garages for storage of loaded commercial trucks, exceeding 2,000 square feet in area and of other than fireproof construction. (f) Bus garages exceeding 2 stories in height. (g) Basement garages housing more than 3 motor vehicles. (h) Garages located in buildings in which one or more stories, or parts thereof, above such garages are occupied for other purposes when such garages have a capacity of 20 or more passenger automobiles, or are used as bus terminals for 2 or more busses, or are used for the storage and loading of 2 or more trucks.. (i) Basements having an area exceeding 3500 square feet, when used for the manufacture, sale or storage of combustible goods or merchandise, except that in public buildings, institutional buildings and residence buildings, the automatic sprinkler equipment will be required only in such portions as are used for storage purposes or as work shops. (j) In buildings occupied as a place of assembly and having a stage arranged for theatrical, operatic or similar purposes, approved automatic sprinkler equipment shall be provided under the roof of the stage, under the gridiron, the rigging loft and fly and tie galleries, under the stage, in dressing rooms, scene docks, workshops and storage rooms. (k) When adequate heat is not provided and in the opinion of the building inspector the hazard is not severe, such sprinkler system may be replaced by a system having approved automatic sprinklers, but with supply only from a fire department connection on the building front, or with an approved protective device with fire department connection on the building front, by which water can be applied to or directed at the fire by suitable control equipmenft from out- side the building; there being in each case an approved automatic fire ailrm system connected to an outside gong or to the center station of a supervising company. SECTION 38. SIGNS AND OUTDOOR DISPLAY STRUCTURES. Page - 30 - (a) No display sign shall hereafter be erected, or attached to, suspended from or supported on a building or structure until a permit for the same has been issued by the building inspector.. No permit for a display sign shall be issued until the required bond has been filed. (b) The owner or persona in contrbl of a display sign suspended over a street or extending into a street more than 15 inches beyond the building line shall execute a bond in a sum to be fixed by the official having control over the streets, with sureties approved by such official, indemnifyirgg the municipality against all loss, cost, damage, or expense incurred or sustained by or recovered against the municipality by reason of the construction or maintenance of such display sign. (c) The provisions of this section, except as to safety shall not apply to a sign not more than 10 square feet in area, announcing, without display or elaboration, only the name of the proprietor and the nature of his display; nor to a wall sign not exceeding one square foot of display sur- face on a residence building stating clearly the name and pro- fession on an occupant; nor to a sign, not exceeding 10 square feet of display surface on a public building giving the name and nature of the occupancy and information as to the conditions of use or admission, nor to a wall sign not exceeding 22 square feet of display surface, not a ground sign, advertising in either case the sale or rental of the premises upon which it is maintained; nor to street signs erected by the municipality; nor to temporary signs or banners legally authorized. PASSED AND APPROVED THIS 24 DAY OF March A. D. 1966. Attest: City Secretary City of Pearland Aprove: 1 yor ity of Pearland Page - 31 - AFFIDAVIT OF PUBLICATION THE STATE OF TEXAS ) COUNTY OF BRAZORIA BEFORE ME, the undersigned authority, a Notary Public in and for said State and County, on this day personally appeared John D. Bowman , being known f o me, and being by me first duly sworn, upon his oath deposes and says: that he is the publisher of THE PEARLAND PROGRESS, a newspaper of general circulation published in Brazoria County, Tex- as: that a copy of the attached notice was published in the English language in said newspaper on the following dates: I�ar.ch__.3.1 196___.6 196 196 196 A.pr.i1 7 196 A copy of such notice being attached hereto and expressly made a part of this affidavit of publisher or other duly authorized person. THE PEARLAND PROGRESS BY: }hzz.. A.• - -.8 oilman Publisher, The Pearland Progress SWORN TO AND SUBSCRIBED before me by the said , publisher of The Pear - land Progress, on this the 16 day of May 19 66 to certify which witness my hand and seal of office. John D. Bow an L. S. Notary Public in and for Brazoria ColInty, Texas Marvin MCGGJatJliry ORDINANCE NO. 116 BUILDING CODE OF THE CITY OF PEARLAND PEARLAND, TEXAS AN ORDINANCE T.O BE CALLED "BUILDING CODE OF THE CITY OF PEAR - LAND CREATING ABUILD- ING CODE PRESCRIBING DUTIES AND QUALIFICA- TIONS OF OFFICIAL; PRO- VIDING FOR PERMITS DO- ING OR CAUSING TO BE DONE CONTRACT WORK; PRESCRIBING FEES; PRO- VIDING EXCEPTIONS; REGULATING QUALITY; TYPE AND KIND OF MA- TERIAL AND MANNER OF INSTALLATION REFER- RING TO SOUTHERN STAN- DARD BUILDING CODE AND ADOPTING SAME; PROVID=''7 ING FOR APPOINTME, 4'r t OF ,BUILDING INSPECTOR AND INSPECTION Ot'ALI, BUILDING. THIS BUILDING CODE INCLUDES METES AND BOUNDS OR THE CITY OF PEARLAND. ALL BUILDINGS AND REMO- DELING MUST HAVE BUILDING PERMIT, AND MUST ACQUIRE IT FROM CITY SECRETARY OR TAX DEPARTMENT. ON REMODELING OF HOMES OWNER MUST HAVE ELECTRICAL AND PLUMBING INSPECTIONS. THERE WILL BE NO CHARGE IF ALL THREE INSPECTIONS DO NOT EX- CEED $1,000. THE BUILD- ING OFFICIAL MUST IN- SPECT THE BUILDING BE- FORE SLAB IS POURED; AFTER BUILDING DRIES IN SO INSPECTOR CAN SEE CORNER BRACES, COLAR BRACES AND RAFTERS, AND TYPE OF MATERIALS USED. FINAL INSPECTION AFTER JOB IS COMPLET- ED. Passed and approved this the 24th day of March, 19q. Attest: /s/ W. A. McClellan City of Pearland By: /s/John G. Keglc'; Printer's Fee: 19v3-4