Ord. 1211-2005-03-28ORDINANCE NO. 1211
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF
PEARLAND, TEXAS, AMENDING CHAPTER 10, FIRE
PREVENTION AND PROTECTION, OF THE
CITY OF PEARLAND CODE OF ORDINANCES, AS IT MAY
HAVE BEEN, FROM TIME TO TIME, AMENDED, TO AMEND
ARTICLE III, ENTITLED FIRE CODE; HAVING A SAVINGS
CLAUSE, A SEVERABILITY CLAUSE, AND A REPEALER
CLAUSE; AND PROVIDING FOR CODIFICATION AND AN
EFFECTIVE DATE.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF PEARLAND,
TEXAS:
Section 1. That Chapter 10, Fire Prevention and Protection, of the City
of Pearland Code of Ordinances, is hereby amended to AMEND Article III,
entitled Fire Code, to read as follows:
"ARTICLE III. FIRE CODE
10-46. Fire code adopted.
There is hereby adopted the "City of Pearland Fire Code," which shall consist of
the International Fire Code, 2003 Edition, including appendices as published by
the International Code Council, Inc. A copy of said code shall be maintained in
the office of the city secretary.
10-47. Local amendments.
The fire code adopted in Section 10-46 is hereby modified as follows:
(a) The following provisions are added:
(1) 903.2.5.1 Facilities housing individuals incapable of self-
preservation. Any facility other than a foster home that houses
individuals that are incapable of self-preservation, as defined by the
Life Safety Code, N.F.P.A. 101, shall be protected throughout by an
approved N.F.P.A. 72 fire alarm and N.F.P.A. 13 automatic
sprinkler system.
Exceptions:
ORDINANCE NO. 1211
1. In the case of a personal care facility, child-care,
group home, or in -home residential child care that
houses fewer than six clients, including a person who
is incapable of self-preservation, a 13 R or 13 D
automatic sprinkler system shall be acceptable, so
long as the plans for installation are forwarded to the
Fire Marshal for review and permitting.
2. In the case of a personal care facility, child-care,
group home, or in -home residential child care that
houses fewer than six clients, including a person who
is incapable of self-preservation, a residential
automatic fire alarm system with smoke detection
throughout shall be acceptable, so long as the plans
for installation are forwarded to the Fire Marshal for
review and permitting.
(2) 903.2.5.2 Inspection by Fire Marshal. The Pearland Fire
Marshal or his designee shall inspect all registered and licensed
personal care facilities, foster care, child-care, and group homes
within the City of Pearland for compliance with the fire code.
907.7.1 Evacuation. Upon activation of any automatic fire alarm
system, all occupants of the structure shall be evacuated and shall
remain outside the structure until the fire department has
determined that no fire or danger exists. To enable fire department
personnel to locate the area or zone activated, occupants of the
structure shall not reset an alarm activation. A trained individual
with the responsibility to respond to an emergency may only silence
alarm activations if such can be achieved without resetting the
alarm. Only fire department personnel or employees of the fire
alarm company may reset a fire alarm system.
(3)
(4) 2505.8 Off-loading of trucks. All incoming tires by truck or trailer
shall be off-loaded within 24 hours and worked into stock on non-
combustible racks as required for all tire storage. Tires are not to
be left on the ground at the end of the workday and the truck or
trailer transporting the incoming tires shall be removed from the site
immediately following off-loading.
(5)
2505.9 Public nuisance declared. Tires not designated for retail
or wholesale consumption shall not be allowed to accumulate
above the limits herein established regardless of their form,
whether whole, split, shredded, or chopped, or so as to constitute a
fire or health hazard. Any accumulation in violation of this section
shall be deemed a public nuisance and their prohibition shall
2
ORDINANCE NO. 1211
extend to all of the city's extra -territorial jurisdiction (ETJ) within five
thousand (5,000) feet of the city's corporate limits.
(b) The following provisions are deleted in their entirety:
(1) 905.5.1 Groups A-1 and A-2.
(2) 905.5.2 Protection.
(3) 905.5.3 Class II system 1 inch hose.
(4) 912.2 Location.
(5) D103.6.2 Roads more than 26 feet in width.
(c) The following provisions are adopted in place of the identically numbered
provisions in the International Fire Code, 2000 Edition:
(1) 105.1.1 Permits required. Permits required by this code shall be
obtained from the code official. Permit fees, if any, shall be paid
prior to issuance of the permit. Issued permits shall be kept on the
premises designated therein at all times and shall be readily
available for inspection by the code official. Permits are required
for the following:
Type I Permit (include review, inspection, testing, and permit)
Installation of fire sprinkler system.
Modification of more than 20 sprinkler heads.
Installation of underground fire mains.
Installation of smoke control systems.
Installation of fire pumps.
Installation of standpipe system.
Installation of fixed fire protection systems.
Installation of fire alarm.
Installation or removal of flammable/combustible liquid storage
tank.
Installation of residential automatic fire sprinkler system.
Type II Permits (includes permit and site inspection)
Temporary storage tanks.
Public displays of fireworks.
(2) 307.1 General. No person shall kindle or maintain any type of
open fire or burning, including bonfires, recreational fires, and
3
ORDINANCE NO. 1211
(3)
trench -burn fires as defined by the Texas Commission on
Environmental Quality (TCEQ), within the city. Such open fires are
hereby declared to be a public nuisance, and their prohibition shall
extend to all of the city's extra -territorial jurisdiction (ETJ) within five
thousand (5,000) feet of the city's corporate limits.
This prohibition does not apply to live firefighting training conducted
by the Fire Department in compliance with TCEQ regulations,
barbecue pits used for cooking, or an approved outdoor fireplace
used for warmth that has three sides and a spark arrestor and
complies with Sec. 307. The fire official may prohibit any or all
fires, or order the immediate extinguishment of any and all fires
when, in his sole discretion, atmospheric conditions or local
circumstances make such fires an immediate threat to public safety
or the smoke or ash from such fires becomes a public nuisance.
308.3.1 Open -flame cooking devices. Charcoal burners and
other open -flame cooking devices shall not be operated on
balconies or within 10 feet (3048 mm) of a building.
Exceptions:
1. One- and two-family dwellings.
2. Where the building and the area
where the charcoal burner or open -flame cooking
device is operated, such as a patio, deck, porch, or
balcony, are protected by an automatic sprinkler
system.
Charcoal burners, solid fuel cookers, and barbeque pits shall be
listed for their intended use and shall not be used inside a structure
unless specifically intended or listed for inside use.
(4) 503.3 Marking. Where required by the code official, approved
signs or other approved notices shall be provided for fire apparatus
access roads to identify such roads or prohibit the obstruction
thereof. Signs or notices shall be maintained in a clean and legible
condition at all times and replaced or repaired when necessary to
provide adequate visibility.
Whenever any provision regarding the regulation of fire lanes
contained in the most recent edition of the International Fire Code
adopted by the City is in conflict with the provisions of this
subsection, the provisions of this subsection shall govern.
The owner, manager, or person in charge of any new or existing
building or property for which fire lanes have been approved or
4
ORDINANCE NO. 1211
(5)
required by the Fire Marshal or his authorized representative shall
mark and maintain said fire lanes as provided below.
(a) Fire lanes shall not be located immediately adjacent
to a structure if other possible locations exist that are not
immediately adjacent but close enough to give sufficient
access to at least three sides of the structure. The minimum
corner radius on the turns shall be 25' on the inside and 50'
on the outside.
(b) All curbs and curb ends shall be painted red with
white lettering four inches (4") high and at least one half -inch
(1/2") stroke, stating "NO PARKING - FIRE LANE". Wording
may not be spaced more than twenty five feet (25') apart.
Fire lanes shall be marked on both sides of access roads so
as to assure a minimum of 24' clear width in the middle of
said access roads.
(c) In areas where fire lanes are required but no
continuous curb is available, one of the following methods
shall be used, in conjunction with curb markings where
possible, to indicate that the fire lane is continuous:
(1) Signs that comply with Section D103.6 shall be
mounted conspicuously along the edge of the fire
lane, spaced no more than twenty-five feet (25') apart,
and shall have lettering at least two inches (2") high
with three -eighths inch (3/8") stroke.
(2) From the point the fire lane begins to the point
the fire lane ends, including behind all parking spaces
which adjoin a fire lane, there shall be painted one
continuous red stripe having a minimum width of at
least six inches (6"). Fire lanes shall be stenciled
every twenty-five feet (25') apart "NO PARKING
FIRE LANE" with white lettering four inches (4") high
and at least one half -inch (1/2") stroke. Fire lanes shall
be so marked on both sides of the lane.
506.1 When required. All new construction or any repair or
alteration to existing buildings with pre-existing monitored fire
protection systems (alarm/sprinkler) where the work costs 50% or
more of the building's value shall be required to have a key box
approved by the Fire Marshal.
5
ORDINANCE NO. 1211
(6) 903.2.5 Group I. An automatic sprinkler system shall be provided
throughout buildings with a Group I fire area, except that an
automatic sprinkler system installed in accordance with Sections
903.3.1.2 or 903.3.1.3 shall be allowed in Group 1-1 facilities. An
automatic residential fire alarm system, equipped with emergency
force notification and initiated by smoke detection and activation of
the automatic sprinkler system, shall also be provided throughout
buildings with a Group I fire area.
(7)
This section shall only apply to the new construction or
registering/licensing of a facility other than a foster home.
903.2.7 Group R. An automatic sprinkler system shall be provided
throughout all buildings with a Group R occupancy fire area,
including attached balconies, patios, porches, breezeways, car
ports, and porte chaches, regardless of fire separations.
(8) 903.2.9 Group S. All storage facilities (S-1/S-2) moderate/low-
hazard that are 5000 sq. ft. or more shall be fully sprinklered,
regardless of the fire area and aggregate floor area. Installation of
fire separations is not an exception to sprinklers on structures that
have a fire area greater than 5000 sq. ft.
(9)
903.3.7 Fire department connections. The fire department
connection (FDC) shall be located at a point no further than 20 feet
from a fire apparatus access road, remotely located at a horizontal
distance that is greater than the height of the building on the main
street side, and easily accessible to the Fire Department. The
location of the FDC shall be such so as to provide hose
connections that shall not block access to the building or obstruct
other fire apparatus from accessing the building. There shall be an
approved sign as specified by the Fire Marshal designating the
address served by the FDC. A fire hydrant shall be located within
one hundred feet (100') of the FDC measured along a fire
apparatus access road. FDCs shall have a five inch (5") Storz
connection and shall include an approved locking cap as specified
by the Fire Marshal.
(10) 904.3.5 Monitoring. Where a building fire alarm system is
installed, automatic fire -extinguishing systems shall be monitored
by the building fire alarm system in accordance with NFPA 72. If
the building has no fire alarm, a local electronic or mechanical
alarm shall be required to indicate when the system has activated.
(11) 905.1 General. Standpipe systems shall be provided in new
buildings and structures in accordance with this section. Fire hose
6
ORDINANCE NO. 1211
threads used in connection with standpipe systems shall comply
with NFPA 1963 or as otherwise approved and shall be compatible
with fire department hose threads. The location of fire department
hose connection shall be approved. In buildings used for high -piled
combustible storage, fire protection shall be in accordance with
Chapter 24. When a standpipe system is required only a Class I or
Class III standpipe with a 2 1/2" to 1 1/2" reducer attached shall be
acceptable.
(12) 905.5 Location near auditorium. In Group A-1 and A-2
occupancies with occupant loads of more than 1,000, Class I or
Class III hose connections shall be located on each side of any
stage, on each side of the rear of the auditorium, on each side of
the balcony, and on each tier of dressing rooms.
(13) 907.1 General. This section covers the application, installation,
performance and maintenance of fire alarm systems and their
components in new and existing buildings and structures. The
requirements of Section 907.2 are applicable to new building and
structures. The requirements of Section 907.3 are applicable to
existing buildings and structures.
All new installations of residential automatic fire alarm systems
shall comply with the latest published edition of NFPA 72. Said
installations shall include smoke detectors in all sleeping rooms, in
the hallway outside the sleeping rooms, and one per floor. The
detectors shall be interconnected and electrically hard wired with
battery backup in the alarm system.
(14) 907.1.2 Equipment. Systems and their components shall be listed
and approved for the purpose for which they are installed. All new
fire alarm systems installed in structures with more than one story
or larger than 5000 square feet shall be addressable and
communication devices shall be compatible for emergency force
notification. The system shall have occupant notification
throughout the building in compliance with ADA requirements, and
manual pull stations shall be required by all exits regardless of any
conflicting provision in the code.
(15) 907.2 Where required -new buildings and structures. An
approved manual, automatic, or manual and automatic fire alarm
system shall be provided in new buildings and structures in
accordance with Sections 907.2.1 through 907.2.23. Where
automatic sprinkler protection installed in accordance with Section
903.3.1.1 or 903.3.1.2 is provided and connected to the building fire
7
ORDINANCE NO. 1211
alarm system, automatic heat detection required by this section
shall not be required.
An approved automatic fire detection system shall be installed in
accordance with the provisions of this code and NFPA 72.
Devices, combinations of devices, appliances and equipment shall
comply with Section 907.1.2. The automatic fire detectors shall be
smoke detectors, except that an approved alternative type of
detector shall be installed in spaces such as boiler rooms where,
during normal operation, products of combustion are present in
sufficient quantity to actuate a smoke detector.
When the installation of a new fire alarm system is required in any
type of occupancy, said system shall be equipped with one means
of automatic activation, such as smoke detection, heat detection, or
fire sprinklers, in addition to manual operation of the fire system.
All new installations shall be monitored for emergency force
notification and for integrity by means of a dedicated first phone
line.
(16) 907.2.1.1 System initiation in Group A occupancies with an
occupant load of 300 or more. All new and existing assembly
buildings with an occupant load of 300 or greater shall install
Emergency Voice Evacuation (EVAC) systems in accordance with
NFPA 72.
(17) 907.15 Monitoring. Where required by this chapter, an approved
supervising station in accordance with NFPA 72 shall monitor fire
alarm systems. All alarm activations monitored by an approved
supervising station shall not be subject to pre -qualification. Instead,
the local fire department shall immediately be notified of all alarm
activations.
Exception: Supervisory service is not required for automatic
sprinkler systems in one- and two-family dwellings.
(18) 1014.1 Exit or exit access doorways required. All assembly,
business, mercantile, educational, and hazardous occupancies with
more than 50 foot of travel distance to an exit doorway from any
portion of the building shall be provided with two means of egress
that are remotely separated (not on the same plane). All egress
doors must swing in the direction of the exit travel.
(19) 2505.8 Location of storage. Storage of waste tires in any form,
whether whole, split shredded, or chopped, shall only be allowed in
8
ORDINANCE NO. 1211
no more than one (1) enclosed trailer, 8' x 8' x 20' or 1280 ft.3,
located on -site.
(20) D103.6.1 Posting of fire lanes. Fire access roads that are
required to be marked shall have a minimum width of 24 feet and
shall be posted on both sides as a fire lane.
(21) D107.1 One or two-family residential developments.
Developments of one or two-family dwellings where the number of
dwelling units exceeds sixty (60) shall be provided with a separate
and approved fire apparatus access road, and shall meet the
requirements of Section D104.3.
Exceptions:
(1) Where there are 60 or more units on a single public or
private access way and all dwelling units are
protected by an approved residential sprinkler system,
access from two directions shall not be required.
(2) The number of dwelling units on a single fire
apparatus access road shall not be increased unless
fire access apparatus roads will be connected with
future development, as determined by the fire code
official.
10-48. Life safety code adopted.
NFPA 101, Life Safety Code Handbook, 2003 edition, is hereby adopted and
incorporated herein and made a part of hereof for all intents and purposes, and
shall apply for repairs, alterations, renovations, and maintenance of all
commercial buildings and appurtenances thereto. A copy of said code shall be
maintained in the office of the city secretary.
10-49. Penalty for violation.
(a) Any person, firm or corporation who violates or fails to comply with the
requirements or provisions of the "City of Pearland Fire Code," as herein
adopted, shall be deemed guilty of a misdemeanor, and shall, upon conviction by
a court of competent jurisdiction, be punished as provided in section 1-11 of this
Code.
(b) In prosecutions under this section, the requirement that a culpable mental
state be pled and proven by the state is hereby waived."
9
ORDINANCE NO. 1211
Section 2. Savings. All rights and remedies which have accrued in
favor of the City under this Ordinance and amendments thereto shall be and are
preserved for the benefit of the City.
Section 3. Severability. If any section, subsection, sentence, clause,
phrase or portion of this Ordinance is for any reason held invalid, unconstitutional
or otherwise unenforceable by any court of competent jurisdiction, such portion
shall be deemed a separate, distinct, and independent provision and such
holding shall not affect the validity of the remaining portions thereof.
Section 4. Repealer. All ordinances and parts of ordinances in conflict
herewith are hereby repealed but only to the extent of such conflict.
Section 5. Codification. It is the intent of the City Council of the City of
Pearland, Texas, that the provisions of this Ordinance shall be codified in the
City's official Code of Ordinances as provided hereinabove.
Section 6. Effective Date. The City Secretary shall cause this
Ordinance, or its caption and penalty, to be published in the official newspaper of
the City of Pearland, upon passage of such Ordinance. The Ordinance shall
then become effective on June 1, 2005.
PASSED and APPROVED on FIRST READING this the 28th day of
March , A.D., 2005.
TOM REID
MAYOR
10
ORDINANCE NO. 1211
PASSED and APPROVED ON the SECOND AND FINAL READING this the 28th
day of March , A. D., 2005.
ATTEST:
UNG
YSRETAR
APPROVED AS TO FORM
DARRIN M. COKER
CITY ATTORNEY
11
TOM REID
MAYOR
VOTING RECORD SECOND AND FINAL READING
March 28, 2005
Voting "Aye" - Councilmembers Cole, Marcott, Viktorin,
Owens, and Tetens.
Voting "No" - None.
Motion passes 5 to 0.
PUBLICATION DATE:
EFFECTIVE DATE:
April 20, 2005
April 29, 2005
PUBLISHED AS REQUIRED BY SECTION 3.10 OF
THE CHARTER OF THE CITY OF PEARLAND, TEXAS
,.
AFFIDAVIT OF PUBLICATION
The Pearland Reporter News
2404 South Park
Pearland, Texas 77581
4
State of Texas
Brazoria and Harris Counties
ors-�d1(
I, Randy Emmons, hereby certify that the notice hereby appended was published
vr.
in Brazoria and Harris Counties in THE REPORTER NEWS, a newspaper of general.
circulation in Brazoria, Harris & Galveston Counties, for % j issues, as follows:
No. / {Date 7 ' 62-° 20 03-
No Date 20
No. Date 20
No. Date 20
No. Date 20
Subscribe and sworn to before me this .)-/
20_
LAURA ANN EMMONS
Notary Public, State of Texas
Commission Expires 09-09-2006
..� o o o o o e.....0 t• .. •-• ......•. •'• .. o o • o, • •
day. of
Laura Ann Emmons, Publisher
Notary Public, State of Texas
r .Published April 20, 2005
-ORDINANCE NO.1211
_
• AN ORDINANCE OF THE
CITY COUNCIL OF THE ,
1 CITY, OF . PEARLAND,
TEXAS, ' AMENDING
CHAPTER.10, FIRE PRE-
, VENTION AND PROTEC-
TION;, OF• THE CITY 'OF,
, PEARLAND CODE OF;
i ORDINANCES, AS IT MAY
HAVE BEEN, FROM TIME
B TO TIME, AMENDED,10 section ,1 11 of this Code.
AMEND .ARTICLE.III, ENTI-
i TLED FIRE CODE; HAV- PASSED and APPROVED
ING A SAVINGS CLAUSE, , ON FIRST READING this
A S E V E R A B I L I T Y; f the 28th day of March,
CLAUSE, AND A REPEAL- ; A.D., 2005. '
.ER CLAUSE;.AND PRO-
VIDING FOR •CODIFICA-
1TION AND AN EFFECTIVE ) ayoReid
DATE. Mayor
10.49. Penalty for viola- i
tion. I
- (a) Any -person, firm or cor-
poration who violates or
fails to comply with the
requirements or provisions
of the "City of Pearland Fire
Code," as herein adopted,
shall be deemed guilty of a
misdemeanor, and shall,
upon conviction by a court
of competent jurisdiction, be
punished as provided in
ATTEST:
/s/ Young Lorfing, TRMC
City Secretary
PASSED and APPROVED
on the SECONC and FINAL
READING this the 28th day
of March, A.D., 2005.
/s/Tom Reid
Mayor.
ATTEST:
/s/ Young Lorfing, TRMC •
City Secretary •
APPROVED AS TO FORM:
/s/ Darrin M. Coker
City Attorney
VOTING RECORD SEC-
OND AND FINAL READING
March 28.2005
Voting "Aye" - Councilmem-
bers Cole, Marcott, Viktorin,
Owens and Tetens.
Voting' "No"-- None.
Motion passes 5 to 0.
PUBLICATION DATE:
April 20, 2005
EFFECTIVE DATE:
April 29, 2005 •-
PUBLISHED AS RE-1
QUIRED BY SECTION 3.10;
' OF THE CHARTER OF
THE CITY OF PEARLAND,
TEXAS.